HLP-A100 Series Operating Manual
HLP-A100 Series
-
14
-
3.3.3 Installation and Direction
Single Installation
The inver ter must be installed
vertically with smooth ventilation.
Enough space must be lef t around
the inverter to ensure good cooling,
as shown below:
Min:100 mm
Min:100 mm
Side by Side Installation
HLP-A100 series inverter can be
mounted side by side, a minimum
space must be reserved above and
below the enclosure, as shown below:
Fig.1 Single installation
Fig.2 Side by side installation
Model
Fuse(Rated current/A) Main Circuit Terminals
HLP-A100003743
125
M8
HLP-A100004543
160
M8
HLP-A100005543
160
M8
HLP-A100007543
224
M8
HLP-A100009043
300
M10
HLP-A100011043
350
M10
HLP-A100013243
400
M10
HLP-A100016043
500
M12*1 (M10*2)
HLP-A100018543
630
M12*1 (M10*2)
HLP-A100020043
630
M12*1 (M10*2)
HLP-A100022043
800
M12*1 (M10*2)