HLP-A100 Series
HLP-A100 Series Operating Manual
-
49
-
Item Parameter
No.
Function
Description
Setting range
Unit
Default
setting
Page
No.
C16.90
Alarm Word
0~0xFFFFFFFFUL
132
C16.91
Alarm Word
2
0~0xFFFFFFFFUL
133
C16.92
Warning
Word
0~0x7FFFFFFFUL
133
C16.93
Warning
Word 2
0~0x7FFFFFFFUL
134
Pa
ram
et
er G
rou
p 2
5: A
pp
. f
un
ctio
ns C
as
cad
e
C25.00 Cascade Mode
0: Normal cascade;
1: Water level control;
0
134
C25.03
Fixed Speed
Pump
Number
0~2
0
134
C25.10 Multi Pressure
Selection
0: Disable; 1: Enable;
0
134
C25.11 Present Time 0.00~23.59
h
0.00
134
C25.12 Multi Pressure
Time
0.00~23.59
h
0.00
135
C25.20 Cascade Low
Frequency
0.000~400.000
Hz 20.000
135
C25.21
Low
Frequency
Delay Time
0.0~3600.0
s
20.0
135
C25.25 Cascade High
Frequency
0.000~400.000
Hz 50.000
136
C25.26
High
Frequency
Delay Time
0.0~3600.0
s
20.0
136
C25.30
Low Pressure
Warning
Level
0.000~99.999
kg
3.000
136
C25.31
Low Pressure
Warning
Delay Time
0.0~3600.0
s
10.0
136
C25.32
Recovery
Low Pressure
Level
0.000~99.999
kg
4.000
136