HLP-A100 Series Operating Manual
HLP-A100 Series
-
140
-
C25.41 Function Description
Range
Unit
Default Setting
Pump Continous Run
Time
0.0~3600.0
h
12.0
Function: When only one of the two auxiliary pump running, in order to
balance the two auxiliary pump run time, when one of the two
lag pumps continues run time reach to the” Pump Continous Run
Time”, the drive will switch to the other lag pump .
C25.40 Function Description
Range
Unit
Default Setting
Pump Interlock Time
0.0~3600.0
s
5.0
Function: Set the interlock time of the two auxiliary pumps when they
switch to each other.
C25.4* Pump InterLock
C25.50 Function Description
Range
Unit
Default Setting
Sleep Mode
0~1
1
Option: [0]: Disable;
[1]: Enable;
Function: If [0] is selected, the inverter can’t enter sleep mode.
C25.51 Function Description
Range
Unit
Default Setting
Sleep Pressure Level
0~150.0
%
95.0
Function: Define the sleep pressure level of the main pump. Sleep Pressure =
Target Pressure*Sleep Pressure Level.
C25.5* Sleep Mode