13. Troubleshooting
13-98
Table 13-44 Analog output module troubleshooting
Operational error
Check
Corrective action
The correct electrical
voltage and current are
not output.
Are there any problems with the analog
output installation?
Correct the installation.
Are there any mistakes in the terminal block
installation?
Correctly install the terminal block.
Are there any problems in the output cabling? Correct the cabling.
Are there any mistakes in the grounding?
Correctly ground the system.
Are there any mistakes in the output channel? Output data to the correct channel.
When mode 1 is specified, is the analog
module registered in the CPU module?
Use the tools to register the analog module
specified for mode 1.
Is the RANGE switch set incorrectly?
Set the switch correctly.
Errors other than the
above
Does the error persist, even after the above
corrective action has been taken?
Replace the relevant module.
Содержание S10VE
Страница 1: ...User s Manual General Description SEE 1 001 A ...
Страница 2: ...User s Manual General Description ...
Страница 27: ...S 24 Revision History Revision No History revision details Issue date Remarks A New edition Oct 2019 ...
Страница 53: ...This page is intentionally left blank ...
Страница 59: ...This page is intentionally left blank ...
Страница 67: ...This page is intentionally left blank ...
Страница 75: ...This page is intentionally left blank ...
Страница 77: ...This page is intentionally left blank ...
Страница 103: ...This page is intentionally left blank ...
Страница 129: ...This page is intentionally left blank ...
Страница 295: ...This page is intentionally left blank ...
Страница 309: ...This page is intentionally left blank ...
Страница 341: ...This page is intentionally left blank ...
Страница 345: ...This page is intentionally left blank ...
Страница 475: ...This page is intentionally left blank ...
Страница 489: ...This page is intentionally left blank ...
Страница 505: ......
Страница 506: ...This page is intentionally left blank ...