13. Troubleshooting
13-86
If a timeout occurs intermittently in a station module connected to the remote I/O line, follow the
instructions in Figure 13-22 to troubleshoot the problem.
Figure 13-22 Troubleshooting procedure for intermittent timeouts
Replace the module with the address
for which the timeout occurred.
Finish
Check and correct the problem according to
Table 13-37 Detailed check items 4
. Correct
any mistakes.
Check the saved data for the system register
status.
Yes
No
a
In the logged area for the system
register status, are there any areas in
which a timeout occurred?
Yes
No
b
Go to
b
in the troubleshooting
flow shown in Figure 13-21.
Has the timeout been eliminated?
Содержание S10VE
Страница 1: ...User s Manual General Description SEE 1 001 A ...
Страница 2: ...User s Manual General Description ...
Страница 27: ...S 24 Revision History Revision No History revision details Issue date Remarks A New edition Oct 2019 ...
Страница 53: ...This page is intentionally left blank ...
Страница 59: ...This page is intentionally left blank ...
Страница 67: ...This page is intentionally left blank ...
Страница 75: ...This page is intentionally left blank ...
Страница 77: ...This page is intentionally left blank ...
Страница 103: ...This page is intentionally left blank ...
Страница 129: ...This page is intentionally left blank ...
Страница 295: ...This page is intentionally left blank ...
Страница 309: ...This page is intentionally left blank ...
Страница 341: ...This page is intentionally left blank ...
Страница 345: ...This page is intentionally left blank ...
Страница 475: ...This page is intentionally left blank ...
Страница 489: ...This page is intentionally left blank ...
Страница 505: ......
Страница 506: ...This page is intentionally left blank ...