7. Wiring
7-4
■ 4-point terminal block
Solderless terminal type: M3
Applicable module name: Power supply (100 V AC or DC)
Applicable module model: LQV410
Tightening torque: 0.6 N-m
Figure 7-3 4-point terminal block
■ Compatible solderless terminals
You must use M3 terminals (such as V1.25-3 and 1.25-YS3A) for the solderless terminals.
Figure 7-4 Compatible solderless terminal
The cable sheath ends and the wire ends that connect to the solderless terminals must be protected to prevent
inadvertent contact. You might use an insulating cap, heat-shrunk tube, or insulating tape, for example.
Figure 7-5 Connecting solderless terminals to cables
Cable
Heat-shrunk tube or other
means of protection
Solderless
terminals
Shielded cable
Spade terminal
Example: 1.25-YS3A
Tightening torque: 0.6 N-m
6 mm
Ring type terminal
Example: V1.25-3
Tightening torque: 0.6 N-m
7 mm
or less
7 mm
or less
4-M3
9.5
1.3
41.5
8.2
3
.8
Unit
:
mm
Содержание S10VE
Страница 1: ...User s Manual General Description SEE 1 001 A ...
Страница 2: ...User s Manual General Description ...
Страница 27: ...S 24 Revision History Revision No History revision details Issue date Remarks A New edition Oct 2019 ...
Страница 53: ...This page is intentionally left blank ...
Страница 59: ...This page is intentionally left blank ...
Страница 67: ...This page is intentionally left blank ...
Страница 75: ...This page is intentionally left blank ...
Страница 77: ...This page is intentionally left blank ...
Страница 103: ...This page is intentionally left blank ...
Страница 129: ...This page is intentionally left blank ...
Страница 295: ...This page is intentionally left blank ...
Страница 309: ...This page is intentionally left blank ...
Страница 341: ...This page is intentionally left blank ...
Страница 345: ...This page is intentionally left blank ...
Страница 475: ...This page is intentionally left blank ...
Страница 489: ...This page is intentionally left blank ...
Страница 505: ......
Страница 506: ...This page is intentionally left blank ...