GK600E User Manual
Chapter 6 List of Parameters
- 79 -
Parameter
Designation
Scope
Factory
default
Attr
9: Multi-step speed
10: Communication
b0-04
Auxiliary FREQ digital
setting
Low er limit FREQ ~ upper limit FREQ 0.00Hz
△
b0-05
Auxiliary FREQ range
0: Relative to maximum FREQ
1: Relative to master FREQ
0
×
b0-06
Auxiliary FREQ coeff
0.0%~100.0%
100.0%
×
b0-07
Computation of master and
auxiliary FREQ
0: auxiliary
1: Master - auxiliary
2: Max {master, auxiliary}
3: Min {master, auxiliary}
0
×
b0-08
Maximum FREQ
Upper limit FREQ ~600.00Hz
50.00Hz
×
b0-09
Upper limit FREQ
Low er limit FREQ ~ maximum FREQ
50.00Hz
×
b0-10
Low er limit FREQ
0.00Hz~upper limit FREQ
0.00Hz
×
b0-11
Operation w hen set FREQ
low er than low er limit
FREQ
0: Run at low er limit FREQ
1: Run at 0 Hz
2: Stop
0
×
b0-12
Time-delay of stop w hen
set FREQ low er than low er
limit FREQ
0.0s ~ 6553.5s
0.0s
×
b0-13
Low er limit of skip FREQ
band 1
0.00Hz~upper limit FREQ
0.00Hz
×
b0-14
Upper limit of skip FREQ
band 1
0.00Hz~upper limit FREQ
0.00Hz
×
b0-15
Low er limit of skip FREQ
band 2
0.00Hz~upper limit FREQ
0.00Hz
×
b0-16
Upper limit of skip FREQ
band 2
0.00Hz~upper limit FREQ
0.00Hz
×
b0-17
Low er limit of skip FREQ
band 3
0.00Hz~upper limit FREQ
0.00Hz
×
b0-18
Upper limit of skip FREQ
band 3
0.00Hz~upper limit FREQ
0.00Hz
×
b0-19
Jog FREQ
0.00Hz~upper limit FREQ
5.00Hz
△
Group b1 Start/Stop Control
b1-00
Run command
0: Control panel control
1: Terminal control
2: Communication control
1
×