Chapter 6 List of Parameters GK600E User Manual
- 106 -
Parameter
Designation
Scope
Factory
default
Attr
(SUE)
29: EEPROM read/w rite fault (EPr)
30: Contactor close fault (CCL)
31: Port communication abnormal
(TrC)
32: Control panel communication
abnormal (PdC)
33: Parameter copy fault (CPy)
34: Reserved
35: Softw are version compatibility
fault (SFt)
36: CPU interference as a fault (CPU)
37: Overcurrent reference fault (oCr)
38: 5V pow er supply out-of-limit
(SP1)
39: 10V pow er supply out-of-limit
(SP1)
40: AI input out-of-limit (AIP)
41: Undervoltage protection (LoU)
42-44: Reserved
45: PID feedback loss (PIo)
46: Profibus communication
abnormal (PFS)
U1-01
Run frequency at fault 1 0.00Hz~600.00Hz
0.00Hz
◎
U1-02
Output current at fault 1
0.0A~6553.5A
0.0A
◎
U1-03
Bus voltage at fault 1
0V~10000V
0V
◎
U1-04
Temperature 1 of heat sink
at fault 1
-40.0
℃
~100.0
℃
0.0
℃
◎
U1-05
Temperature 2 of heat sink
at fault 1
-40.0
℃
~100.0
℃
0.0
℃
◎
U1-06
Input terminal status at fault
1
0~FFFF
0000
◎
U1-07
Output terminal status at
fault 1
0~FFFF
0000
◎
U1-08
Cumulative run time at fault
1
0h~65535h
0h
◎
U1-09
Code of fault 2
Same as U1-00
0
◎
U1-10
Run frequency at fault 2
0.00Hz~600.00Hz
0.00Hz
◎
U1-11
Output current at fault 2
0.0A~6553.5A
0.0A
◎
U1-12
Bus voltage at fault 2
0V~10000V
0V
◎
U1-13
Temperature 1 of heat
sink at fault 2
-40.0
℃
~100.0
℃
0.0
℃
◎