Chapter 5 Elevator Dedicated Parameters GK600E User Manual
- 66 -
Applies to general constant-torque load. When drive output frequency is 0, output voltage w ill
be 0, w hile w hen output frequency is rated frequency of motor, the output voltage w ould be
rated voltage of motor.
1: Broken line V/f (determined by d1-01~d1-08)
Applies to elevator, spin drier, centrifuge, industrial w ashing machine and other special loads.
When drive output frequency is 0, output voltage w ill be 0, w hile w hen output frequency is
rated frequency of motor, the output voltage w ould be rated voltage of motor. What is
different is this pattern can set 4 inflection points by d1-01~d1-08. See Fig. 5-3.
Fig. 5-3 User-defined multi-stage V/f curve
V0, V1, V2, V3 and f0, f1, f2 and f3 in the figure are voltage value and frequency value set by
parameters d1-01~d1-08.
2: 1.2nd pow er
3: 1.4th pow er
4: 1.6th pow er
5: 1.8th pow er
6: 2.0th pow er
Parameter values 2~6 apply to torque-dropped loads such as fans and w ater pumps. See
Fig. 6-42.
7: V/f separated pattern 1
Output frequency and output voltage can be set separately. Frequency is set by the method
as stated in Group b0. Output voltage is set by d1-18. See d1-18 for details. This mode
applies to variable-frequency pow er supply or torque motor control etc.
8: V/f separated pattern 2
Determine a certain voltage by linear V/f mode, and then multiply this voltage by the
proportion set by d1-18 to obtain drive output voltage. See d1-18 for details.
d1-01
V/f frequency value f3
Range: 0.00Hz~rated frequency
of motor
Factory default:
50.00Hz
d1-02
V/f voltage value V3
Range: 0.0%~100.0%
Factory default:
100.0%