Chapter 4 Operation and Run Instructions GK600E User Manual
- 42 -
Indicator
Designation
Meaning
OFF: Stop
Flash: Stopping
FWD
Forw ard indicator
ON: If the drive in stop status, forw ard command
enabled. If the drive in run status, the drive is
running forw ard
Flash: Forw ard is being transferred to reverse
REV
Reverse indicator
ON: If the drive in stop status, reverse command
enabled. If the drive in run status, the drive is
running reversely.
Flash: Reverse is being transferred to forw ard
4.1.3 Control Panel Display Status
Control panel indicates eight types of status, STOP parameters display, Run parameters
display, Fault display, parameter number edition, parameter setting, Passw ord authentication,
Direct frequency modification and Prompt message. The operation relating to these statuses
and the sw itching among these statuses is described as follow s.
4.1.3.1 Display of STOP Parameters
The drive normally gets into STOP parameters display once run has been stopped. By default,
set frequency is displayed in such a status, and other parameters can be displayed through
setting of L1-02 parameters and the
key. For example, w hen users need to check set
frequency as w ell as the values of bus voltage and AI1 value in stop status, set L1-02=0013
(refer to setting method of parameters) and press the
key to display the value of bus
voltage and then press
again to display the value of AI1.
Fig. 4-2 Stop parameter display status (Displaying setting frequency
– 50.00Hz)
Run status w ill be enabled immediately upon receipt of run command in stop status. Press