GK600E User Manual
Chapter 5 Elev ator Dedicated Parameters
- 63 -
Group C1 Digital Output
In elevator application, a relay output is often used to control run contactor, another relay output
controls the brake, w hile a digital output reports the fault. As default configuration and setting,
GK600E has a relay output at its control board to control the brake, and a relay output at its
option board EPC-TM1 to control the run contactor.
C1-00
Y1 output function
Range: 0~99
Factory default: 14
C1-01
Y2/DO output function
(w hen used as Y2)
Range: 0~99
Factory default: 0
C1-02
Control board relay
output function
Range: 0~99
Factory default: 27
C1-03
Option board relay
output function
Range: 0~99
Factory default: 35
14: Fault output
27: Brake control
35: RUN contactor control
For more information of different parameter values, please refer to the complete parameter list
in Chapter 6.
Group d0 Motor Parameters
d0-00
Motor type
Range: 0~1
Factory default: 1
0: Ordinary motor
1: Variable frequency motor
The major difference betw een ordinary motor and variable frequency motor depends on the
handling of motor overload protection. Under low speed run, ordinary motor has poor heat
dissipation, so motor overload protection shall be derated at low speed. Since fan-based heat
dissipation of variable frequency motor is not affected by motor speed, low -speed overload
protection is not necessarily derated. Therefore, please set d0-00 to 0 w hen driving ordinary
asynchronous motor so as to protect the motor reliably.
d0-01
Motor pow er rating
Range:
0.4kW~6553.5kW
Factory default:
model dependent
d0-02
Motor rated voltage
Range: 0V~480V
Factory default: 380V
d0-03
Motor rated current
Range: 0.0A~6553.5A
Factory default:
model dependent
d0-04
Motor rated freq
Range: 0.00Hz~upper
limit frequency
Factory default:
50.00Hz