GK600E User Manual
Chapter 5 Elev ator Dedicated Parameters
- 71 -
F1-07
Multi-step frequency 5
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-08
Multi-step frequency 6
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-09
Multi-step frequency 7
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
Multi-speed frequency 0 till multi-speed frequency 7 sets
frequency references (Hz) of the drive. The
selection of any of the above reference is performed by the dedicated selectors (Multi-speed
Sel 1 to 3).
Multi-speed Sel
3
Multi-speed Sel
2
Multi-speed Sel
1
Frequency reference
OFF
OFF
OFF
Multi-speed frequency 0(F1-02)
OFF
OFF
ON
Multi-speed frequency 1(F1-03)
OFF
ON
OFF
Multi-speed frequency 2(F1-04)
OFF
ON
ON
Multi-speed frequency 3(F1-05)
ON
OFF
OFF
Multi-speed frequency 4(F1-06)
ON
OFF
ON
Multi-speed frequency 5(F1-07)
ON
ON
OFF
Multi-speed frequency 6(F1-08)
ON
ON
ON
Multi-speed frequency 7(F1-09)
GK600E have follow ing default setting:
X1 for Enable C0-01=71
X2 for Fw d C0-02=3
X3 for Rev C0-03=4
X4 for multi-speed sel 1 C0-04=15
X5 for multi-speed sel 2 C0-05=16
X6 for multi-speed sel 3 C0-06=17
Group F6: Elevator Control Mode
F6-00
Lift control mode
Range: 0000~1111
Factory default:
0101
Ones place: Brake control
0: Disabled
1: Enabled
Tens place: Logic of elevator and motor run direction
0: Positive logic
1: Negative logic
Hundred place : Motor run enable signal