Chapter 4 Operation and Run Instructions GK600E User Manual
- 52 -
Flow chart is shown below:
Fig. 4-13 Flow chart of user parameter initialization
Exam ple 3
: setting method of hexadecimal parameter
Take L1-02 (LED STOP display parameter) for example, if LED control panel is required to
display: setting frequency, bus voltage, AI1, running linear speed, and setting linear speed.
Since all bits are independent of each other, the ones place, tens place, hundreds place and
thousands place should be set separately. Determine the binary numbers of each bit and then
convert the binary numbers into a hexadecimal number. See Table 4-6, the corresponding
relation betw een binary numbers and a hexadecimal number.
Table 4-6 Corresponding relation between binary and hexadecimal
Binary numbers
Hexadecimal
(LED bit display value)
BIT3
BIT2
BIT1
BIT0
0
0
0
0
0
0
0
0
1
1
0
0
1
0
2
0
0
1
1
3
0
1
0
0
4
0
1
0
1
5
0
1
1
0
6
0
1
1
1
7
1
0
0
0
8
1
0
0
1
9
1
0
1
0
A
1
0
1
1
B
1
1
0
0
C
1
1
0
1
D
1
1
1
0
E
1
1
1
1
F
Set the value in the ones place:
As show n in Fig. 4-14, "setting frequency" and "bus voltage" are respectively determined by
50.00
ENT
A0-0
0
A0-0
3
0
2
或
3
A0-00
50.00
▲
ENT
▲
ENT
ESC
2 or 3