Chapter 3 Installation and Wiring GK600E User Manual
- 32 -
Control cables shall be kept no less than 20cm aw ay from main circuit and strong current lines
(e.g. pow er lines, motor lines, relay lines and contactor lines) and should not be arranged in
parallel w ith strong current lines. In case it is inevitable to intersect strong current line, vertical
w iring is recommended to avoid drive faults as a result of noise.
Where analog input & output signals are severely interfered, the side of analog signal source
should be provided w ith filter capacitor or ferrite core.
3.9.4 Instructions of Digital Input/Output Terminals
Digital input & output signal cables should be as short as possible, shielded, and their shielded
layers should be properly grounded close to the side of drive. The cables should not exceed
20m. When active drive is selected, take necessary filtering measures against pow er crosstalk,
for w hich dry contact control is recommended.
Control cables shall be kept no less than 20cm aw ay from main circuit and strong current lines
(e.g. pow er lines, motor lines, relay lines and contactor lines) and should not be arranged in
parallel w ith strong current lines. In case it is inevitable to intersect strong current line, vertical
w iring is recommended to avoid drive faults as a result of noise. Operating instructions for
sw itching value input terminal
Instructions of digital input terminal
Dry contact
1
6
X1
X6/DI
COM
+24V
PLC
+3.3V
GND
24V
Drive
External
Controller
Shielded
Cable
Near-end
Ground
+
-
Jumper
OC
+3.3V
GND
+
-
OC
Fig. 3-14 Internal power supply dry contact