GK600E User Manual
Chapter 5 Elev ator Dedicated Parameters
- 73 -
F6-09
Brake close frequency
Range: 0.00Hz~10.00Hz
Factory default:
0.2Hz
F6-11
Brake w aiting time
Range: 0.00s-10.00s
Factory default:
0.4s
Duration of the stopping phase, after the speed has fallen below the zero threshold (F6-09) or
DC brake stop/start frequency (b1-14). During this phase, the inverter can either output a DC
current (default), or maintain a low frequency, in order to compensate for the slip, as
programmed by F6-09.
F6-12
Brake close delay
Range: 0.00s-10.00s
Factory default:
0.1s
Sets time delay betw een the close command and the effective engagement of the mechanical
brake.
F6-13
Contactor close delay
Range: 0.00s-10.00s
Factory default:
0.5s
Sets time delay for safe closing of the run contactor.
F6-14
Contactor open delay
Range: 0.00s-10.00s
Factory default:
0.5s
Sets time delay betw een the open command and the effective opening of the run contactor.
F6-15
Leveling start s-curve time
Range: 0.00s-60.00s
Factory default:
0.00s
F6-16
Leveling end s-curve time
Range: 0.00s-60.00s
Factory default:
0.00s
F6-17
Lift-up leveling linear dec
time
Range: 0.00s-60.00s
Factory default:
5.00s
F6-18
Lift-dow n leveling linear
dec time
Range: 0.00s-60.00s
Factory default:
5.00s
F6-19
Lift-up slip compensation
Range: 0.0%-400.0%
Factory default:
150.0%
F6-19 Sets the amount of slip compensation (% of rated slip, calculated from nameplates) to
improve lift going up leveling w hen required.
F6-20
Lift-dow n slip
compensation
Range: 0.0%-400.0%
Factory default:
60.0%
F6-20 sets the amount of slip compensation (% of rated slip, calculated from nameplates) to
improve lift going dow ning leveling w hen required.