Chapter 5 Elevator Dedicated Parameters GK600E User Manual
- 70 -
When drive output current exceeds the level set by E1-04 and the lasting time attains
parameter value of E1-05, the drive w ill display overload fault and coast to stop.
E1-04
Overload alarm threshold
Range: 20.0%~200.0%
Factory default:
120.0%
When tens place of E1-03 is set to 0, this parameter value is a percentage compared to rated
current of motor. When tens place of E1-03 is set to 1, this parameter value is a percentage
compared w ith rated current of drive.
E1-05
Overload alarm activation
time
Range: 0.1s~60.0s
Factory default:
7.0s
Sets the lasting time that overload alarm is activated w hen output current of drive is bigger than
the threshold set by E1-04.
E1-12
Cooling fan control
Range: 0~1
Factory default: 0
0: Auto run
The fans run all the time during the running. Determine if the fans continue to run or stop
according to module temperature after stop.
1: Alw ays run after pow er up
The fans run all the time after applying pow er to the drive.
E1-13
Drive overheat alarm
threshold
Range: 0.0
℃
~100.0
℃
Factory default:
80.0
℃
This parameter sets the threshold of drive overheat alarm.
Group F1 Multi-step Frequency
Multi-speed references can be defined as high speed, leveling speed, inspection speed
according to different requirements.
F1-02
Multi-step frequency 0
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-03
Multi-step frequency 1
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-04
Multi-step frequency 2
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-05
Multi-step frequency 3
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz
F1-06
Multi-step frequency 4
Low er limit frequency ~ upper
limit frequency
Factory default:
0.00 Hz