UAS 7002 NIU
3-9
GDC 087R706-000-02
5.
Use the arrow keys to toggle the highlighted field through its two potential settings, Masked
and Reported.
6.
When the field displays the desired setting, press the Enter key. The highlight returns to the
Select field. The All Alarms Control field displays Mixed when changes result in a mixture
of Masked and Reported settings.
7.
Repeat steps 4 through 5 for each option you need to change.
8.
After you’ve made all required changes and you are certain they are correct, type S and
press the Enter key to save your configuration changes. Then press the Enter key a second
time, to return to the Alarm Configuration submenu screen.
If you decide to leave the Alarm Masks configuration screen without putting changes into
effect, press the Enter key without first typing S.
9.
If you need to make any adjustments to performance alarm intervals or thresholds, go to the
appropriate Alarms Thresholds configuration screen. Type 2 for the near-end thresholds or
3 for the far-end thresholds, and press the Enter key. If you don’t need to set thresholds,
go to step 16.
Each Alarms Thresholds screen has a Time Interval and a Count Threshold, each with its
own selection number, for every performance alarm. The threshold is the number of events
required to generate the alarm, and the interval is the time span in which the threshold value
must be reached.
10.
Type the Time Interval selection number for an alarm you need to configure, and press the
Enter key. Highlighting appears on the corresponding current setting field.
11.
Use the arrow keys to toggle the highlighted field through its potential settings: Not Used;
1, 10, or 30 Seconds; 1 or 15 Minutes; 1 or 24 Hours; or Infinite. Not Used causes the unit
to disregard the value in the threshold field and report the alarm on each occurrence of the
condition. Infinite permits the count to continue until it reaches the threshold. Press the En-
ter key when the selected setting is displayed.
12.
Type the Count Threshold selection number for the alarm you are configuring, and press
the Enter key. Highlighting appears on the corresponding current setting field.
13.
Use the arrow keys to toggle the highlighted field through its potential settings: 1, 3, 10,
100, 1000, or 10000. Press the Enter key when the selected setting is displayed.
14.
Repeat steps 10 – 13 for each performance alarm you are configuring to be Reported.
15.
After you’ve made all required changes and you are certain they are correct, type S and
press the Enter key to save your configuration changes. Then press the Enter key a second
time, to return to the Alarm Configuration screen.
If you decide to leave the Alarms Thresholds configuration screen without putting changes
into effect, press the Enter key without first typing S.
16.
To dismiss the Alarm Configuration screen, type selection 0,
Return to Main Menu,
and press the Enter key.