2-10
UAS 7001 NIU
GDC 087R706-000-02
6.
When the field displays the desired setting, press the Enter key. The highlight returns to the
Select field. The All Alarms Control field displays Mixed when changes result in a mixture
of Masked and Reported settings.
7.
Repeat steps 4 through 5 for each option you need to change.
8.
After you’ve made all required changes and you are certain they are correct, type S and
press the Enter key to save your configuration changes. You may use either upper or lower
case for letter responses. Then press the Enter key a second time, to return to the Alarm
Configuration Submenu screen.
If you start to leave the Alarm Masks configuration screen while there are unsaved changes,
the screen displays
*WARNING - EXITING WITHOUT SAVING CHANGES Continue? [ ] Y(es), N(o)
You can type
N
and press the Enter key to keep the screen on display while you perform a
save, or you can type
Y
and press the Enter key to finish exiting. Unsaved changes are lost
if you exit without performing a save.
9.
If you need to make any adjustments to performance alarm intervals or thresholds, type 2
and press the Enter key to go to the Performance Alarms Thresholds Configuration Sub-
menu screen. If not, go to step 16.
The Performance Alarms Thresholds Configuration Submenu screen has a Time Interval
and a Count Threshold, each with its own selection number, for every performance alarm.
The threshold is the number of events required to generate the alarm, and the interval is the
time span in which the threshold value must be reached.
10.
Type the Time Interval selection number for an alarm you need to configure, and press the
Enter key. Highlighting appears on the corresponding current setting field.
11.
Use the arrow keys to toggle the highlighted field through its potential settings: Not Used;
1, 10, or 30 Seconds; 1 or 15 Minutes; 1 or 24 Hours; or Infinite. Not Used causes the unit
to disregard the value in the threshold field and report the alarm on each occurrence of the
condition. Infinite permits the count to continue until it reaches the threshold. Press the En-
ter key when the selected setting is displayed.
12.
Type the Count Threshold selection number for the alarm you are configuring, and press
the Enter key. Highlighting appears on the corresponding current setting field.
13.
Use the arrow keys to toggle the highlighted field through its potential settings: 1, 3, 10,
100, 1000, or 10000. Press the Enter key when the selected setting is displayed.
14.
Repeat steps 10 – 13 for each performance alarm you are configuring to be Reported.
15.
After you’ve made all required changes and you are certain they are correct, type S and
press the Enter key to save your configuration changes. Then press the Enter key a second
time, to return to the Alarm Configuration screen.
If you start to leave the Alarm Thresholds configuration screen while there are unsaved
changes, the screen displays
*WARNING - EXITING WITHOUT SAVING CHANGES Continue? [ ] Y(es), N(o)
You can type
N
and press the Enter key to keep the screen on display while you perform a
save, or you can type
Y
and press the Enter key to finish exiting. Unsaved changes are lost
if you exit without performing a save.
16.
To dismiss the Alarm Configuration screen, type selection 0,
Return to Main Menu,
and press the Enter key.