ADL500 • Quick installation guide - Specifications and connection
91
●
Fast Input Inputs (Freeze)
Description
Features
Type
24V
dc
PNP Input
Input voltage
0 to + 24 V
dc
(+30 V
dc
max)
Load
8mA @ 24V
dc
, RL = 2.7kΩ
Thresholds
V
il
< 2V, V
ih
> 19V
Isolation
Yes, functional (>1kV)
+24VDC
2k7
2
FH1
+24VDC
2k7
1
FH2
0V
3
FH1
FH2
X
E
●
STO Input signal (Safe Torque Off)
Description
Features
Type
24V
dc
Operating voltage
0 to +
24V
dc
(+
36V
dc
max)
Load
20mA @ +
24V
dc
- R
l
= 1.32 kΩ
Thresholds
V
ic
<
5V
dc
– V
ih
>
18V
dc
Isolation
Yes, functional (>1kV)
●
STO Output signal (Safe Torque Off)
Description
Features
Type
24V
dc
or 110
V
ac
Operating voltage
0 to+
24V
dc
(+
36V
dc
max) or 0 to +
110V
ac
(+
125V
ac
max)
Load
200mA @ +
24V
dc
(250
max
)
or 200 mArms @
110
V
ac
(250 max)
Thresholds
V
ic
<
5V
dc
– V
ih
>
18V
dc
Max blocking voltage
400V
A.2.1 Selection of Voltage/Current at analog input
Analogue input 1 is factory set for differential voltage signals (-10V..+10V).
To change the input type (0.20mA, 0.10V or 4.20 mA) it is necessary to change the (PAR 1602
Analog inp 1 type
,
menu ANALOG INPUTS) parameter setting and the position of P2 Jumper as shown in the figure.
To access the adjustment card, remove the top cover, see section "A.1 - Optional cards" on page 87.
Regulation card
OFF
= Voltage
(Default)
ON
= Current
Содержание ADL500