ADL500 • Quick installation guide - Specifications and connection
85
Index
Error message shown on
the display
Sub-code
Description
49
During automatic phasing a communication channel is activated between the drive and encoder. An error has occurred on this com-
munication channel.
Solution:
Repeat the procedure.
Solution:
If the message has a value other than 0 follow the instructions provided for each case and repeat automatic phasing.
6
Power config
Condition:
may occur during recognition of power cards. If this message is displayed, it is not possible to drive the motor.
0020H-32
The power card is configured for a drive that is incompatible with the regulation card
0021H-33
The configuration of the power card is not compatible with the regulation card
0017H-23
The configuration required is not available on the power card
Solution:
Download the correct configuration on the power card
7
Save par failed
Condition:
during transfer of the parameters from the drive to the memory of the keypado
0H-0
Communication error
0023H-35
Communication error
0023H-36
Communication error
0025H-37
The data saved on the keypad are not valid
Solution:
8
Load par failed
Condition:
during transfer of the parameters from the memory of the keypad to the drive
9
Load par incomplete
0H-0
Communication error
0023H-35
Communication error
0023H-36
Communication error
0025H-37
The data saved on the keypad are not valid.
No parameter is transferred from the keypad to the drive
0026H-38
Incompatible drive series.
No parameter is transferred from the keypad to the drive
0027H-39
Incompatible software version.
All the parameters present in the memory of the keypad have been transferred to the drive. The set of parameters transferred refers to
a drive with a different firmware version; therefore, certain parameters may not be updated.
0028H-40
Incompatible drive size.
All the parameters present in the memory of the keypad (excluding those that depend on the size of the drive), have been transferred to
the drive. The parameters that depend on size maintain their original value.
0029H-41
Error during saving of parameters on the drive.
All the parameters present in the memory of the keypad have been transferred to the drive. The transfer of one or more parameters has
caused an “out of range” error, or one or more parameters does not exist. At the end of transfer, one or more parameters may not have
been updated.
002AH-42
PLC application release and version not compatible.
All parameters in the keypad memory have been transferred to the drive.
The transferred set of parameters relates to a drive with a PLC application in which the version and release of the application are differ-
ent. As a result some of the PLC application parameters may not be updated.
002BH-43
PLC application not compatible.
All the parameters in the keypad memory except those relating to the PLC applciation have been transferred to the drive.
The transferred set of parameters relates to a drive with a different PLC application. As a result none of the PLC application parameters
are updated.
Solution:
Recover a set of parameters from a compatible drive (model and size)
10
Not used
11
Load def plc
Condition:
may occur during loading of the parameter database saved in the Flash of the Mdplc application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message appears the drive restores the default database, i.e. the one that was downloaded.
0001H-1
The database saved is not valid
Solution:
Set the parameters to the value required and perform
Save parameter
12
Plc cfg error
Condition:
may occur during loading of the Mdplc application
The Mdplc application present on the drive is not run.
0004H-4
The application downloaded has a different Crc on DataBlock and Function table
0065H-101
The application downloaded has an invalid identifier (Info)
0066H-102
The application downloaded has an incorrect task number (Info)
0067H-103
The application downloaded has an incorrect software configuration
0068H-104
The application downloaded has a different Crc on DataBlock and Function table
0069H-105
A Trap error or System error has occurred.
The drive automatically performs a Power-up operation.
The application is not run.
See in Alarm List for further information regarding the error occurred
006AH-106
The application downloaded has an incorrect identifier (Task)
006BH-107
The application downloaded has an incorrect task number (Task)
006CH-108
The application downloaded has an incorrect Crc ( Code)
Solution:
Remove the Mdplc application or download a correct Mdplc application
13
Plc 1
Reserved messages and dedicated to the PLC application. See the application manual.
14
Plc 2
15
Plc 3
16
Plc 4
17
Opt bus fault
Condition:
this may occur when the drive is turned on, during fieldbus card setup. Error during configuration or communication error.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is 0, the error regards a communication problem.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is other than 0, the error regards a configuration problem.
Solution:
For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address, parameter setting
For communication errors, check wiring, termination resistors, disturbance immunity, timeout settings.
For further details, please refer to the user guide for the specific bus.
18
Wrong key
Condition
: this may occur when powering the drive, if the incorrect enable key is inserted for a given firmware function.
xxxxH-x
Solution
: Ask Gefran to supply the correct key to enable the desired firmware function.