5 - Options
5.1 External fuses
5.1.1 Network side fuses (F1)
The inverter must be fused upstream on the network side.
Use fast-acting fuses only.
Size
F1 - External network side fuses
DC link capacitor hours of
service life [h]
EUROPE
AMERICA
Type
Code
Type
Code
ADL5...-...-4, 3ph
1040
> 15000
GRD2/20
F4D15
A70P20
S7G48
1055
> 15000
GRD2/25
F4D16
A70P25
S7G51
1075
> 15000
GRD3/35
F4D20
A70P40
S7G52
2110
> 15000
Z22GR40
F4M16
A70P40
S7G52
2150
> 15000
Z22GR63
F4M17
A70P60-4
S7I34
Technical data for fuses, including dimensions, weights, power leakage, fuse carriers etc. are reported in the corresponding manufacturers' data sheets:
GRD... (E27), S00... = Jean Müller, Eltville; A70...= Ferraz.
5.2 Input chokes
The three-phase mains choke is strongly recommended in order to:
- limit the RMS input current of the ADL500 inverter.
- increase the life of intermediate circuit capacitors and reliability of input diodes.
- reduce mains harmonic content
- reduce problems due to power supply via a low impedance line (≤ 1%).
In accordance with EN 12015 (THD values < 35%), provide the following:
- sizes ≤ 22kW: DC input inductance (see paragraph 5.2.2)
- sizes ≥ 30kW: AC input inductance (see paragraph 5.2.1).
5.2.1 AC input chokes
Size
Effective input current I
n
(@400V/50Hz, with AC input chokes)
(A)
Model
Code
Dimensions:
Width x Height x Depth
mm [inches]
Weight
kg [lbs]
ADL5...-...-4, 3ph
1040
9
LR3y-2040
S7AAG
120 x 125 x 65 [4.7 x 4.9 x 2.6]
2 [4.4]
1055
13.5
LR3y-2055
S7AB5
120 x 125 x 75 [4.7 x 4.9 x 2.6]
2.2 [4.4]
1075
18
LR3y-2075
S7AB6
150 x 155 x 79 [5.9 x 6.1 x 3.1]
4.9 [10.8]
2110
24
LR3y-3110
S7AB7
150 x 155 x 79 [5.9 x 6.1 x 3.1]
5 [11]
2150
32
LR3y-3150
S7AB8
150 x 169 x 85 [5.9 x 6.7 x 3.3]
5.5 [12.1]
5.2.2 DC input chokes
Size
Effective input current I
n
(with external DC chokes)
External DC chokes
@230V/50Hz @400V/50Hz @480V/50Hz
Rated
current
Overload
current
Model
Code
Dimensions:
Width x Height x Depth
Weight
(A)
(A)
(A)
(Arms)
(*) (Arms)
mm [inches]
kg [lbs]
ADL5...-...-4, 3ph
1040
8
8
7.5
10
20
LDC-004
S7AI10
99 x 96 x 93 [3.90 x 3.78 x 3.66]
2.4 [5.3]
1055
12
12
11
16
31
LDC-005
S7AI11
125 x 112 x 98 [4.92 x 4.41 x 3.86]
4.1 [9.0]
1075
16
16
14
21
41
LDC-007
S7AI12
125 x 127 x 122 [4.92 x 5.00 x 4.80]
4.9 [10.8]
2110
21
21
18
28
54
LDC-011
S7AI13
125 x 127 x 142 [4.92 x 5.00 x 5.59]
6.6 [14.6]
2150
28
28
25.5
36
70
LDC-015
S7AI14
125 x 127 x 152 [4.92 x 5.00 x 5.98]
8 [17.6]
(*) 10s every 60s.
Max room operating temperature = 50°C [122°F].