72
ADL500 • Quick installation guide - Specifications and connection
03/07
PAR:
2100
Encoder pulses
1024
ppr
Def:
1024
Range: 4 ... 16384
04/07
PAR:
2110
Encoder signal check
Check A-B
Value:
1
Available selections:
(1) Check A-B
(2) Check A-B-Z
At the end of the procedure proceed to next step.
Step 3 – Setting motor parameters
Note !
Def:
The factory (default) setting depends on the size of the drive that is connected. These values refer to the size ADL5.-1055
STARTUP WIZARD
Set motor data?
E=Yes
Down=Next
E
01/09
PAR:
540
Control type
SYN FOC
Value:
2
Available selections:
(2) SYN FOC
02/09
PAR:
2000
Rated voltage
340
v
Def:
400
Range: 230 ... 480V
03/09
PAR:
2002
Rated current
17.5
a
Def:
11.8
Range: 1 ... 1500A
04/09
PAR:
2004
Rated speed
144
rpm
Def:
1450
Range: 10 ... 32000rpm
06/09
PAR:
2008
Pole pairs
12
Def:
2
Range: 1 ... 60
09/09
PAR:
2014
Torque constant
50.00
N
m
/a
Def:
50.00
Range: -
Set the plate data of the motor connected, following the instructions given on the previous pages.
Rated voltage [V]:
the rated voltage of the motor indicated on the data plate.
Rated current [A]:
motor rated current; approximately, the value should not be less than 0.3 times the rated current of the drive, output current
class 1 @ 400 V on the data plate of the drive.
Rated speed [rpm]:
motor rated speed; see data plate.
Pole pairs:
Number of motor pole pairs; see data plate.
Torque constant [Nm/a] :
(KT) Ratio between the torque generated by the motor and the current required to supply it.
Note !
When data entry is complete the
Take parameters
command is executed automatically (menu MOTOR DATA, PAR: 2020). The motor data entered during the
STARTUP WIZARD procedure are saved in a RAM memory to enable the drive to perform the necessary calculations.