16
ADL500 • Quick installation guide - Specifications and connection
4.6.3 K
t
: Ambient temperature reduction factor
Figure 4.6.3
: Tamb reduction coefficient
1.00
T amb (°C)
K
T
-10
40 50
0
0.90
1.00
T amb (°C)
K
T
-10
40 50
0
ADL550
ADL510/ADL530
Function not allowed
Range of ambient
temperatures allowed
4.7 Voltage level of the inverter for safe operations
The minimum time
between the moment in which an ADL500 inverter is disabled from the mains and that in which an
operator can operate on internal parts of the inverter, without the danger of electric shock,
is 5 minutes
.
This value takes into account the time to turn off an inverter supplied at 460 Vac + 10%, without any options (time indicated for disabled
inverter condition).
4.8 No-load consumption (Energy rating)
Size
No. of pre-loads allowed
Power-on
time
[secs]
Stand-by consumption
"Fan Off"
[W]
Fan consumption
[W]
Stand-by consumption
"Fan On"
[W]
ADL5...-...-4, 3ph
1040
1 each 20 sec.
5 abt.
20
8
28
1055
1 each 20 sec.
5 abt.
20
10
30
1075
1 each 20 sec.
5 abt.
20
10
30
2110
1 each 20 sec.
5 abt.
20
10
30
2150
1 each 20 sec.
5 abt.
20
16
36
4.9 Cooling
Size
Pv
(Heat dissipation)
Fan capacity
Minimum cabinet opening for
cooling
@U
ln
=230...460V
ac
(*)
Heat sink (m
3
/h)
Internal (m
3
/h)
(cm
2
)
ADL5...-...-4, 3ph
1040
150
2 x 35
-
72
1055
250
2 x 58
-
144
1075
350
2 x 58
-
144
2110
400
2 x 58
-
144
2150
600
2 x 58
-
328
(*) values that refer to operation at default switching frequency.
Attention