ADL500 • Quick installation guide - Specifications and connection
19
5.3 AC output chokes
The ADL500
inverter can be used with standard motors or motors designed specifically for use with inverters.
The latter usually have a higher isolation rating to better withstand PWM voltage Examples of reference regulations
are provided below: motors designed for use with inverters do not require any specific filtering of output from the
inverter. For standard motors, especially with long cable runs (typically over 100 m) an output choke may be necessary
to maintain the voltage waveform with the specified limits.
The range of recommended chokes are listed in the following table. The rated current of the chokes should be approx.
20% higher than that of the inverter in order to take into account additional losses due to modulation of the output
waveform.
Size
Model
Code
Dimensions:
Width x Height x Depth
mm [inches]
Weight
kg [lbs]
ADL5...-...-4, 3ph
1040
LU3-005
S7FG3
180 x 170 x 110 [7.1 x 6.7 x 4.3]
5.8 [12.8]
1055
LU3-005
S7FG3
180 x 170 x 110 [7.1 x 6.7 x 4.3]
5.8 [12.8]
1075
LU3-005
S7FG3
180 x 170 x 110 [7.1 x 6.7 x 4.3]
5.8 [12.8]
2110
LU3-011
S7FG4
180 x 180 x 130 [7.1 x 7.1 x 5.1]
8 [17.6]
2150
LU3-015
S7FH2
180 x 160 x 170 [7.1 x 6.3 x 6.7]
7.5 [16.5]
Note !
With the inverter operated at the rated current and a frequency of 50 Hz, the output chokes cause a voltage drop of approx. 2% of the output voltage.
5.4 External braking resistors
Recommended combinations for use with internal braking unit.
Table 5.4.1: Recommended combination
Size
List and technical data of standard external resistors
Resistor type
Code
Q.ty
Max. overload,
1" - service 10%
E
br
(kJ)
Max. overload,
30" - service 25%
E
br
(kJ)
P
nbr
(W)
R
br
(
Ω
)
Housing
Dimensions:
Width x Height x
Depth (mm)
Weight
(kg)
ADL5...-...-4, 3ph - LOW DEMAND
1040
RFPR 750 D 68R
S8SZ3
1
7.5
38
425
68
IP44
245 x 75 x 100
2.7
1055
RFPR 750 D 68R
S8SZ3
1
7.5
38
425
68
IP44
245 x 75 x 100
2.7
1075
RFPR 1200 D 49R
S8SZ4
1
7.5
28
470
49
IP44
310 x 75 x 100
4.2
2110
RFPR 1900 D 28R
S8SZ5
1
12
43
550
28
IP44
365 x 75 x 100
4.2
2150
RFPR 1900 D 28R
S8SZ5
1
12
43
550
28
IP44
365 x 75 x 100
4.2
ADL5...-...-4, 3ph - MID DEMAND
1040
1650
68
1055
1650
68
1075
2250
49
2110
3300
28
2150
4500
28
ADL5...-...-4, 3ph - HIGH DEMAND
1040
2750
68
1055
2750
68
1075
3750
49
2110
5500
28
2150
7500
28
P
nbr
Braking resistor rated power
R
br
Braking resistor ohmic value
E
br
Maximum energy that can be dissipated on the resistor
Braking resistors may be subject to unexpected overloads due to faults.
Resistors MUST be protected using thermal cutouts. These devices must not interrupt the circuit in which the resistor is
inserted but their auxiliary contact must cut off the power supply to the power section of the drive. If the resistor requires a
protection contact, this must be used together with that of the thermal cutout.
A la suite de pannes, les résistances de freinage peuvent être sujettes à des surcharges imprévues. La protection des
résistances au moyen de dispositifs de protection thermique est absolument capitale. Ces dispositifs ne doivent pas inter-
rompre le circuit qui abrite la résistance, mais leur contact auxiliaire doit couper l’alimentation du côté puissance du drive.
Warning!