CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–81
The 469 can detect the phase rotation of the three phase voltage. If the Phase Reversal
feature is turned on when all 3 phase voltages are greater than 50% motor nameplate
voltage, and the phase rotation of the three phase voltages is not the same as the settings,
a trip and block start will occur in 500 to 700 ms.
NOTE
Note
This feature does not work when single VT operation is enabled.
5.10.4 Frequency
PATH: SETTINGS
S9 VOLTAGE ELEM.
FREQUENCY
Once the frequency of the phase AN or AB voltage (depending on wye or delta connection)
is out of range of the overfrequency and underfrequency settings, a trip or alarm will occur.
This feature may be useful for load shedding applications on large motors. It could also be
used to load shed an entire feeder if the trip was assigned to an upstream breaker.
FREQUENCY
[
]
FREQUENCY
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
OVER FREQUENCY
ALARM LEVEL: 60.50
Range: 25.01 to 70.00 Hz in steps of
0.01
MESSAGE
UNDER FREQUENCY
ALARM LEVEL: 59.50
Range: 20.00 to 60.00 Hz in steps of
0.01
MESSAGE
FREQUENCY
ALARM DELAY: 1.0 s
Range: 0.0 to 60.0 s in steps of 0.1
MESSAGE
FREQUENCY
ALARM EVENTS: Off
Range: On, Off
MESSAGE
FREQUENCY
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
OVER FREQUENCY
TRIP LEVEL: 60.50 Hz
Range: 25.01 to 70.00 Hz in steps of
0.01
MESSAGE
UNDER FREQUENCY
TRIP LEVEL: 59.50 Hz
Range: 20.00 to 60.00 Hz in steps of
0.01
MESSAGE
FREQUENCY
TRIP DELAY: 1.0 s
Range: 0.0 to 60.0 s in steps of 0.1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...