CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–89
the breaker or contactor operating time. If an alarm occurs and “Breaker” was chosen as
the starter type, the alarm will be Breaker Failure. If “Contactor” was chosen for starter
type, the alarm will be Welded Contactor. Also, if the starter type chosen is “Breaker”, Trip
Coil Supervision may be enabled. The
SUPERVISION OF TRIP COIL
settings is seen only if the
STARTER TYPE
is “Breaker”.
•
If “52 Closed” is selected, the trip coil supervision circuitry monitors the trip coil circuit
for continuity any time the starter status input indicates that the breaker is closed or
motor current is detected. If that continuity is broken, a Starter Failure alarm will
indicate Trip Coil Supervision.
•
If “52 Open/Closed” is selected, the trip coil supervision circuitry monitors the trip coil
circuit for continuity at all times, regardless of breaker state. This requires an alternate
path around the 52a contacts in series with the trip coil when the breaker is open. See
the following figure for modifications to the wiring and proper resistor selection. If that
continuity is broken, a Starter Failure alarm will indicate Trip Coil Supervision.
FIGURE 5–18: Trip Coil Supervision
5.12.3 Demand
PATH: SETTINGS
S11 MONITORING
CURRENT DEMAND
808
7
2
7
A2.CDR
VALUE OF RESISTOR 'R'
SUPPLY
OHMS
WATTS
48 VDC
125 VDC
250 VDC
10 K
25 K
50 K
2
5
5
TRIP
COIL
TRIP COIL
SUPERVISION
1 TRIP
CONTACT
F11
E2
F1
E11
52a
T
RI
P
C
O
I
L
C
LOS
ED
SUP
ER
V
I
S
I
O
N
"52 Cl
osed
"
52a
TRIP
COIL
TRIP COIL
SUPERVISION
1 TRIP
CONTACT
F11
E2
F1
E11
52a
T
RI
P
C
O
I
L
OP
EN
/
C
LOS
ED
SUP
ER
V
I
S
I
O
N
"52
Open/
Cl
osed
"
W
I
T
H
MULT
I
PL
E
B
REAKER A
U
X
C
O
N
T
AC
TS
TRIP COIL
SUPERVISION
1 TRIP
CONTACT
TRIP
COIL
F11
E2
F1
E11
52a
T
RI
P
C
O
I
L OP
EN
/
C
LOS
ED
SUP
ER
V
I
S
I
O
N
"52
Open/
Cl
osed
"
CURRENT
[
]
DEMAND
CURRENT DEMAND
PERIOD: 15 min.
Range: 5 to 90 min. in steps of 1
MESSAGE
CURRENT DEMAND
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
CURRENT DEMAND
LIMIT: 100 A
Range: 10 to 100000 A in steps of 1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...