5–78
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.10 S9 Voltage Elements
5.10.1 Undervoltage
PATH: SETTINGS
S9 VOLTAGE ELEM.
UNDERVOLTAGE
The
U/V ACTIVE ONLY IF BUS ENERGIZED
settings may be used to prevent nuisance alarms
or trips when the bus is not energized. If this settings is programmed to “Yes”, at least one
voltage must be greater than 20% of the nominal nameplate voltage rating for any alarm/
trip. If the load is high inertia, it may be desirable to trip the motor off-line or prevent it from
starting in the event of a total loss of line voltage. Programming “No” for this settings
ensures that the motor is tripped and may be restarted only after the bus is re-energized.
UNDERVOLTAGE
[
]
U/V ACTIVE ONLY IF
BUS ENERGIZED: No
Range: No, Yes
MESSAGE
UNDERVOLTAGE
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
UNDERVOLTAGE ALARM
PICKUP: 0.85 x RATED
Range: 0.60 to 0.99 x RATED in steps of
0.01
MESSAGE
STARTING U/V ALARM
PICKUP: 0.85 x RATED
Range: 0.60 to 1.00 x RATED in steps of
0.01. Enter “1.00” to turn this
function off.
MESSAGE
UNDERVOLTAGE ALARM
DELAY: 3.0 s
Range: 0.0 to 60.0 s in steps of 0.1
MESSAGE
UNDERVOLTAGE ALARM
EVENTS: Off
Range: On, Off
MESSAGE
UNDERVOLTAGE
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
UNDERVOLTAGE TRIP
MODE: 1-Phase
Range: 1-Phase, 3-Phase
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
UNDERVOLTAGE TRIP
PICKUP: 0.80 x RATED
Range: 0.60 to 0.99 x RATED in steps of
0.01
MESSAGE
STARTING U/V TRIP
PICKUP: 0.80 x RATED
Range: 0.60 to 1.00 x RATED in steps of
0.01. Enter “1.00” to turn this
function off.
MESSAGE
UNDERVOLTAGE TRIP
DELAY: 3.0 s
Range: 0.0 to 60.0 s in steps of 0.1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...