5–22
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.3.5
Reduced Voltage
PATH: SETTINGS
S2 SYSTEM SETUP
REDUCED VOLTAGE STARTING
The 469 can control the transition of a reduced voltage starter from reduced to full voltage.
That transition may be based on “Current Only”, “Current and Timer”, or “Current or Timer”
(whichever comes first). When the 469 measures the transition of no motor current to
some value of motor current, a 'Start' is assumed to be occurring (typically current will rise
quickly to a value in excess of FLA, e.g. 3
×
FLA). At this point, the
REDUCED VOLTAGE START
TIMER
is initialized with the programmed value in seconds.
•
If “Current Only” is selected, when the motor current falls below the user's
programmed Transition Level, transition will be initiated by activating the assigned
output relay for 1 second. If the timer expires before that transition is initiated, an
Incomplete Sequence Trip will occur activating the assigned trip relay(s).
•
If “Current or Timer” is selected, when the motor current falls below the user's
programmed Transition Level, transition will be initiated by activating the assigned
output relay for 1 second. If the timer expires before that transition is initiated, the
transition will be initiated regardless.
•
If “Current and Timer” is selected, when the motor current falls below the user's
programmed Transition Level and the timer expires, transition will be initiated by
activating the assigned output relay for 1 second. If the timer expires before current
falls below the Transition Level, an Incomplete Sequence Trip will occur activating the
assigned trip relay(s).
REDUCED
[
]
VOLTAGE STARTING
REDUCED VOLTAGE
STARTING: Off
Range: On, Off
MESSAGE
ASSIGN CONTROL
RELAYS: Auxiliary3
Range: Auxilary2, Aux2 & Aux3,
Auxiliary3
MESSAGE
TRANSITION ON:
Current Only
Range: Current Only, Current or Timer,
Current and Timer
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Aux2, Trip & Aux2 &
Aux3, Trip & Aux3
MESSAGE
REDUCED VOLTAGE
START LEVEL: 100% FLA
Range: 25 to 300% in steps of 1
MESSAGE
REDUCED VOLTAGE
START TIMER: 200 s
Range: 1 to 600 s in steps of 1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...