1–36
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
STATOR RTD TYPE
: “100 Ohm Platinum”
BEARING RTD TYPE
: “100 Ohm Platinum”
AMBIENT RTD TYPE
: “100 Ohm Platinum”
OTHER RTD TYPE
: “100 Ohm Platinum” – default value
As per the information provided above, there will be six RTDs, two per phase located in the
Stator, and two Bearing RTDs, one to monitor the ambient temperature.
For Stator Overtemperature protection, enter the following settings in the
S8 RTD
TEMPERTURE
RTD 1
to
RTD6
menus:
RTD #1 APPLICATION
: “Stator”
RTD #1 NAME
: “ST Ph A1”
RTD #1 ALARM
: “Unlatched”
ASSIGN ALARM RELAYS
: “Alarm”
RTD #1 ALARM TEMPERATURE
: “135°C”
RTD #1 HIGH ALARM
: “Off”
HIGH ALARM RELAYS
: “Alarm” - default value
RTD #1 HIGH ALARM TEMPERATURE
: “135°C” - default value
RTD #1 ALARM EVENTS
: “On”
RTD #1 TRIP
: “Latched”
RTD #1 TRIP VOTING
: “RTD #5”
ASSIGN TRIP RELAYS
: “Trip”
RTD #1 TRIP TEMPERATURE
: “155°C”
The settings for the other RTDs are entered in similar fashion. Refer to
on page 5–72 for additional settings and additional information on RTD monitoring.
1.4.10 Other Settings
Undervoltage Protection
In addition to the settings illustrated above, there will be cases in motor applications where
additional settings will be required, to monitor other system parameters such as voltage
levels.
The following sub-section will illustrate the procedures to set the 469 Motor Management
Relay to meet those requirements.
Description
Using the same system information, the following example illustrates the steps to set the
469 for Undervoltage protection.
The following settings are provided:
Pickup: 70% of nominal voltage – starting
80% of nominal voltage – running
Time Delay: 13.0 s
Other Considerations
•
The function will be active only if there is voltage in the line feeding the motor, to avoid
nuisance trips due to the lack of voltage. The 469 will consider the bus energized only
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...