5–110
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Voltage Dependent Overload Curves
on page 5–47 for additional details on the
custom overload curves available for Speed2.
5.15.2 Speed2 Undercurrent
PATH: SETTINGS
S14 2-SPEED MOTOR
SPEED2 UNDERCURRENT
The addition of a second Undercurrent trip or alarm level may be useful as it will indicate if
the wrong settings are being used for the wrong speed i.e. normal running current for
Speed 2 may be undercurrent for Speed 1.
5.15.3 Speed2 Acceleration
PATH: SETTINGS
S14 2-SPEED MOTOR
SPEED2 ACCELERATION
MESSAGE
SPEED2 ACL INTERSECT
@MIN Vline: 3.80 x FLA
Range: 2.00 to
SPEED2 ISTALL @ MIN
VLINE
– 0.01 in steps of 0.01
MESSAGE
SPEED2 ISTALL @ 100%
Vline: 6.00 x FLA
Range: 2.00 to 15.00 x FLA in steps of
0.01
MESSAGE
SPEED2 SAFE STALL @
100% Vline: 10.0 s
Range: 0.5 to 999.9 s in steps of 0.1
MESSAGE
SPEED2 ACL INTERSECT
@100% Vline: 5.00 x FLA
Range: 2.00 to
SPEED2 ISTALL @ 100%
VLINE
– 0.01 in steps of 0.01
SPEED2
[
]
UNDERCURRENT
BLOCK SPEED2 U/C
FROM START: 0 s
Range: 0 to 15000 s in steps of 1
MESSAGE
SPEED2 U/C ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
SPEED2 U/C ALARM
PICKUP: 0.70 x FLA
Range: 0.10 to 0.95 x FLA in steps of
0.01
MESSAGE
SPEED2 U/C ALARM
DELAY: 1 s
Range: 1 to 60 s in steps of 1
MESSAGE
SPEED2 U/C ALARM
EVENTS: Off
Range: On, Off
MESSAGE
SPEED2 U/C
TRIP: 0ff
Range: Off, Latched, Unlatched
MESSAGE
SPEED2 U/C TRIP
PICKUP: 0.70 x FLA
Range: 0.10 to 0.99 x FLA in steps of
0.01
MESSAGE
SPEED2 U/C TRIP
DELAY: 1 s
Range: 1 to 60 s in steps of 1
SPEED2
[
]
ACCELERATION
SPEED2 ACCEL. TIMER
FROM START: 10.0 s
Range: 1.0 to 250.0 s in steps of 0.1
MESSAGE
ACCEL. TIMER FROM
SPEED1-2: 10.0 s
Range: 1.0 to 250.0 s in steps of 0.1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...