5–92
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
This feature configures one or more of the output relays as a pulsed output. When the
programmed interval has transpired the assigned relay will be activated for 1 second.
NOTE
Note
This feature should be programmed such that no more than one pulse per second will be
required or the pulsing will lag behind the interval activation.
5.12.5 Loss of Communications
PATH: SETTINGS
S11 MONITORING
LOSS OF COMMS
* Only shown if "LOSS OF COMMS: FUNCTION" selection is not 'Off'.
** Only shown if the Option Code is present.
+ Only shown if "LOSS OF COMMS: FUNCTION" selection is not 'Off' and function type is
"Alarm"
+ +Only shown if "LOSS OF COMMS: FUNCTION" selection is not 'Off' and function type is
"Trip"
When the SR469 relay detects inactivity in communicating with the master, the enabled
port will issue a “Loss of Comms Alarm/Trip” event and operate a combination of output
relays.
The communication inactivity detection shown in “Not Communicating” applies to all four
of the SR469 communication ports.
The detailed causes for “Not Communicating” are displayed in section S13 469 TESTING -
Communication Port Monitor
.
The Loss of Communication Alarm/Trip function can be programmed for Latched or
Unlatched:
• Latched: The programmed output relays and target remain latched until
communications with the master are re-established. The latched alarm/trip can be
manually reset or remotely reset via a Modbus command.
LOSS OF COMMS
]
LOSS OF COMMS
FUNCTION: Off
Range: Off, Latched, Unlatched
MESSAGE
*LOSS OF COMMS
FUNCTION TYPE: Alarm
Range: Alarm, Trip
MESSAGE
*LOSS OF COMMS
PORT: COMP_RS485
Range: COMP_RS485, **AUX_RS485,
**Ethernet-T, **DeviceNet
MESSAGE
+ASSIGN LOSS OF
COMMS RELAY: Alarm
Range: Alarm, Alarm & Aux2, Alarm &
Aux2 & Aux3, Alarm & Aux3,
Aux2, Aux2 & Aux3, Aux3,None
MESSAGE
++ASSIGN LOSS OF
COMMS RELAY: Trip
Range: Trip, Trip & Aux2, Trip & Aux2 &
Aux3, Trip & Aux3
MESSAGE
*LOSS OF COMMS
DELAY: 1 s
Range: 1 to 30 s in steps of 1 s
MESSAGE
+LOSS OF COMMS ALARM
EVENTS: Off
Range: On, Off
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...