CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–21
FIGURE 3–23: Reduced Wiring RTDs
The Hot line would have to be run as usual for each RTD. The Compensation and Return
leads, however, need only be run for the first RTD. At the motor RTD terminal box, the RTD
Return leads must be jumpered together with as short as possible jumpers. The
Compensation leads must be jumpered together at the 469.
Note that an error is produced on each RTD equal to the voltage drop across the jumper on
the RTD return. This error increases with each successive RTD added.
V
RTD
1
=
V
RTD
1
V
RTD
2
=
V
RTD2
+
V
J
3
V
RTD3
=
V
RTD3
+
V
J
3
+
V
J
4
, etc.
This error is directly dependent on the length and gauge of the wire used for the jumpers
and any error introduced by a poor connection. For RTD types other than 10
Ω
Copper, the
error introduced by the jumpers is negligible. Although this RTD wiring technique reduces
the cost of wiring, the following disadvantages must be noted:
1.
There will be an error in temperature readings due to lead and connection resistances.
This technique is
NOT
recommended for 10
Ω
Copper RTDs.
2.
If the RTD Return lead to the 469 or any of the jumpers break, all RTDs from the point
of the break will read open.
3.
If the Compensation lead or any of the jumpers break, all RTDs from the point of the
break will function without any lead compensation.
Two-Wire RTD Lead Compensation
An example of how to add lead compensation to a two wire RTD may is shown in the figure
below.
808
7
22A2.CDR
Hot
Compensation
RTD Return
Compensation
Hot
Hot
Compensation
RTD Return
A1
A2
A3
A4
A5
A6
A7
A8
L1
L2
L3
L4
L5
L6
L7
No connection
469
J1
J2
Motor Control
Terminal Box
Motor
RTD1
+
–
RTD2
+
–
RTD3
+
–
J3
J4
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...