CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–19
The
ACTUAL VALUES
PHASORS
page is a useful troubleshooting tool to identify wiring
errors. Use the phasors displayed by the relay and the tables on pages 6–22 and 6–25 to
determine if VTs and CTs are on the correct phases and their polarity is correct. Problems
arising from incorrect wiring include:
• Extremely high unbalance levels (CTs),
• Erroneous power readings (CTs and VTs),
• Phase reversal trips (VTs).
To correct wiring, simply start the motor and record the phasors. The correct phasors can
be determined using the tables along with recorded phasors, system rotation, VT
connection type, and motor power factor. Note that the phase angle for Va (Vab if delta) is
always assumed to be 0° and is the reference for all angle measurements.
Common problems include:
• Phase currents 180° from proper location (CT polarity reversed)
• Phase currents or voltages 120° or 240° out (CT/VT on wrong phase)
An explanation of how the relay identifies and displays system quantities follows. Assume
that the relay is connected to a balanced three-phase system and that V
A
, V
B
, V
C
, and V
COM
are the relay ID names for terminals G2, H1, H2, and G1, respectively.
When the relay is set for the “Open Delta” VT connection type, voltages are measured at
terminals G2 (V
A
) and H2 (V
C
). The voltage at terminal H1 (V
B
) is not measured; however, the
corresponding system quantity is calculated, assuming a balanced three phase system,
where V
A
+ V
B
+ V
C
= 0, leading to V
B
= –(V
A
+ V
C
). In the
ACTUAL VALUES
VOLTAGE
METERING
page, the 469 displays only phase-to-phase voltages. The relationship between
the displayed and measured quantities is as follows:
Vab = V
A
Vbc = –V
C
Vca = –(V
A
+ V
C
) as calculated
In the
ACTUAL VALUES
PHASORS
page, the relay displays the relationship between
measured quantities. Refer to the figure below for wiring connections.
• The measured voltage phasor between terminals G2 (V
A
) and G1 (V
COM
) is
displayed by the relay as “Va Phasor” and “Vab” by the EnerVista 469 Setup
software. In this case, Va Phasor is equal to the system quantity Vab.
• The voltage measured between terminals H1 (V
C
) and G1 (V
COM
) is displayed by the
relay as “Vc Phasor” and “Vcb” by the EnerVista 469 Setup software. In this case, Vc
Phasor is equal to the system quantity Vcb or –Vbc.
• The voltage between H2 (V
B
) and G1 (V
COM
) is zero. Hence, the relay displays a
vector with no magnitude.
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...