CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–7
CT secondary: .................................................1 A or 5 A (specify with order)
Burden:................................................................Less than 0.2 VA at rated load
Conversion range:..........................................0.05 to 20
×
CT
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy: ...........................................................at < 2
×
CT: ±0.5% of 2
×
CT
at
≥
2
×
CT: ±1% of 20
×
CT
CT withstand: ..................................................1 second at 80
×
rated current,
2 seconds at 40
×
rated current, continuous at 3
×
rated
current
RTD INPUTS
3 wire RTD Types: ..........................................100
Ω
Platinum (DIN.43760), 100
Ω
Nickel, 120
Ω
Nickel,
10
Ω
Copper
RTD sensing current: ....................................5 mA
Isolation: .............................................................36 Vpk (isolated with analog inputs and outputs)
Range:..................................................................–50 to +250°C
Accuracy: ...........................................................±2°C
Lead resistance: .............................................25
Ω
Max per lead for Pt and Ni type; 3
Ω
Max per lead for
Cu type
No sensor:..........................................................>1000
Ω
Short/low alarm: ............................................<–50°C
TRIP COIL SUPERVISION
Applicable voltage: .......................................20 to 300 V DC / V AC
Trickle current: ................................................2 to 5 mA
VOLTAGE INPUTS
VT ratio:...............................................................1.00 to 300.00:1 in steps of 0.01
VT secondary: .................................................273 V AC (full-scale)
Conversion range: .........................................0.05 to 1.00
×
full scale
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy: ...........................................................±0.5% of full scale
Max. continuous: ...........................................280 V AC
Burden:................................................................>500 k
Ω
Sensor supply: ................................................+24 V DC at 20 mA max.
2.2.2
Outputs
ANALOG CURRENT OUTPUT
Type: .....................................................................Active
Range:..................................................................4 to 20 mA, 0 to 1 mA
(must be specified with order)
Accuracy: ...........................................................±1% of full scale
Max. load:...........................................................4 to 20 mA input: 1200
Ω
0 to 1 mA input: 10 k
Ω
Isolation: .............................................................36 V
pk
(isolated with RTDs and analog inputs)
4 Assignable Outputs: ..................................phase A, B, and C current; three-phase average current;
ground current; phase AN (AB), BN (BC), and CN (CA)
voltages; three-phase average voltage; hottest stator
RTD; hottest bearing RTD, hottest other RTD; RTDs 1 to 12;
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...