CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–9
Timing accuracy: ...........................................<100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
GROUND INSTANTANEOUS OVERCURRENT
Pickup level: ......................................................0.1 to 1.0
×
CT primary in steps of 0.01
Time delay:........................................................0 to 1000 ms in steps of 10
Pickup accuracy: ...........................................as per ground current input
Operate time (0 ms time delay): ..............<25 ms @ 60 Hz (I > 1.5 x Pickup)*
<30 ms @ 50 Hz (I > 1.5 x Pickup)*
Timing accuracy: ...........................................+50 ms
Elements:............................................................Trip and Alarm
* Applies if Voltage phase A detected, Motor Status Running and frequency within 5% of
nominal (<50ms if these conditions are not met).
JOGGING BLOCK
Starts/hour:.......................................................1 to 5 in steps of 1
Time between starts: ..................................0 to 500 min.
Timing accuracy: ...........................................±0.5 s or ± 0.5% of total time
Elements:............................................................Block
MECHANICAL JAM
Pickup level: ......................................................1.01 to 3.00
×
FLA in steps of 0.01 of any one phase,
blocked on start
Time delay:........................................................1 to 30 s in steps of 1
Pickup accuracy: ...........................................as per phase current inputs
Timing accuracy: ...........................................±0.5 s (Note 1)
Elements:............................................................Trip
OVERLOAD / STALL PROTECTION / THERMAL MODEL
Overload curves: ...........................................15 standard overload curves, custom curve, voltage
dependent custom curve for high inertia starting (all
curves time out against average phase current)
Biasing:................................................................Phase unbalance
Hot/cold curve ratio
Stator RTD
Running cool rate
Stopped cool Rate
Line voltage
Overload pickup: ...........................................1.01 to 1.25 (for service factor)
Pickup accuracy: ...........................................as per phase current Inputs
Timing accuracy: ...........................................±100 ms or ±2% of total time (Note 1)
Elements:............................................................Trip and Alarm
OVERVOLTAGE
Pickup level: ......................................................1.01 to 1.10
×
rated in steps of 0.01 of any one phase
Time delay:........................................................0.1 to 60.0 s in steps of 0.1
Pickup accuracy: ...........................................as per voltage inputs
Timing accuracy: ...........................................±100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...