CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–7
condition that has caused the alarm is still present (e.g. hot RTD) the Alarm relay(s) will
not reset until the condition is no longer present. If on the other hand, an unlatched
alarm feature becomes active, that alarm will reset itself (and associated output
relay(s)) as soon as the condition that caused the alarm ceases. As soon as an alarm
occurs, the alarms messages are updated to reflect the alarm and the 469 display
defaults to that message. Since it may not be desirable to log all alarms as events,
each alarm feature may be programmed to log as an event or not. If an alarm is
programmed to log as an event, when it becomes active, it is automatically logged as
a date and time stamped event.
•
BLOCK START:
A 469 Block Start prevents or inhibits the start of the motor based on
some logic or algorithm. The Block Start feature is always assigned to the Block Start
relay. In addition to the Trip relay(s), a trip always operates the Block Start relay. If the
condition that has caused the trip is still present (e.g. hot RTD), or there is a lockout
time when the
RESET
key is pressed, the Block Start relay will not reset until the
condition is no longer present or the lockout time has expired. Blocking features are
always unlatched and reset immediately when conditions that caused the block
cease. In addition to becoming active in conjunction with trips, a block may become
active once the motor stops. There are several features that operate as such: Starts/
Hour, Time Between Starts, Start Inhibit, Restart Block, and 469 Not Programmed.
Block messages are updated to reflect the block when it becomes active (complete
with lockout time if required) and the screen defaults to that message. Blocks are
normally not logged as events. If however, a motor start or start attempt is detected
when a block is active, it is automatically logged as a date and time stamped event.
This scenario might occur if someone shorts across the block terminals and overrides
the 469 protection to start the motor.
5.1.3
Relay Assignment Practices
There are six output relays. Five of the relays are always non-failsafe, the other (Service) is
failsafe and dedicated to enunciate internal 469 faults (these faults include settings
Corruption, failed hardware components, loss of control power, etc.). One of the output
relays is dedicated as the Block Start relay; it is dedicated to features that are intended to
block motor starting. The four remaining relays may be programmed for different types of
features depending on what is required. One of the relays, 1 TRIP, is intended to be used as
the main trip relay. Another relay, 4 ALARM, is intended to be used as the main alarm relay.
The two relays that are left, 2 AUXILIARY and 3 AUXILIARY, are intended for special
requirements.
When assigning features to Auxiliary Relays 2 and 3, it is a good idea to decide early on
what is required since features that may be assigned may conflict. For example, if
2 AUXILIARY is to be used for upstream trips, it cannot also be used for the control of a
Reduced Voltage Start. Similarly, if 3 AUXILIARY is to be dedicated as a relay to echo all
alarm conditions to a PLC, it cannot also be used strictly to enunciate a specific alarm such
as Undercurrent.
In order to ensure that conflicts in relay assignment do not occur, several precautions have
been taken. All trips with the exception of the Short Circuit Backup Trip default to the 1 TRIP
output relay. All alarms default to the 4 ALARM relay. Only special control functions are
defaulted to Auxiliary Relays 2 and 3. It is recommended that these assignments be
reviewed once all the settings have been programmed.
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...