CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–29
These settings apply only if the
INPUT 1(4) FUNCTION
is “Remote Trip”.
Once the Remote Trip function is chosen for one of the assignable digital inputs, the
settings messages shown here will follow the assignment message. A trip relay may be
selected and the name of the trip may be altered. A contact closure on the digital input
assigned as Remote Trip will cause a trip within 100 ms with the name that has been
chosen. Multiple sources may be used to trigger a remote trip by paralleling inputs.
FIGURE 5–4: Remote Alarm/Trip from Multiple Sources
Speed Switch Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Speed Switch Trip”.
When this function is assigned to a digital input, the following will occur. When a transition
from stopped to start is detected a timer will be loaded with the delay programmed. If that
delay expires before a contact closure is detected, a trip will occur. Once the motor is
stopped, the scheme is reset.
Load Shed Trip
PATH: SETTINGS
S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1(4)
These settings apply only if the
INPUT 1(4) FUNCTION
is “Load Shed Trip”.
Once the load shed trip function is chosen for one of the assignable digital inputs, the
settings messages shown here will follow the assignment message. A trip relay may be
selected. A contact closure on the switch input assigned as load shed trip will cause a trip
within 100 ms.
808
7
16A1.CDR
RE
MOT
E
PUS
H-
BUTTO
N
46
9
Di
g
i
ta
l I
nput
D
ry contact from other dev
i
ce
ASSIGNABLE [
]
INPUT 1
INPUT 1 FUNCTION:
Speed Switch Trip
Range: See above.
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
SPEED SWITCH TRIP
TIME DELAY: 5.0 s
Range: 1.0 to 250.0 s in steps of 0.1
ASSIGNABLE [
]
INPUT 1
INPUT 1 FUNCTION:
Load Shed Trip
Range: See above
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...