CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–103
5.14.3 Fault Setup
PATH: SETTINGS
S13 469 TESTING
FAULT SETUP
The values entered under Fault Values will be substituted for the measured values in the
469 when the simulation mode is “Simulate Fault”.
FAULT
[
]
SETUP
FAULT CURRENT
PHASE A: 0.00 x CT
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT CURRENT
PHASE B: 0.00 x CT
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT CURRENT
PHASE C: 0.00 x CT
Range: 0.00 to 20.00 x CT in steps of
0.01
MESSAGE
FAULT GROUND
CURRENT: 0.0 A
Range: 0.0 to 5000.0 A in steps of 0.1
MESSAGE
FAULT VOLTAGES
VLINE: 1.00 x RATED
Range: 0.00 to 1.10 x RATED in steps of
0.01
MESSAGE
FAULT CURRENT
LAGS VOLTAGE: 0°
Range: 0 to 359° in steps of 1
MESSAGE
FAULT DIFF AMPS
IDIFF: 0.00 x CT
Range: 0.00 to 1.10 x RATED in steps of
0.01
MESSAGE
FAULT STATOR
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT BEARING
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT OTHER
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT AMBIENT
RTD TEMP: 40°C
Range: –50 to 250°C in steps of 1
MESSAGE
FAULT SYSTEM
FREQUENCY: 60.0 Hz
Range: 45.0 to 70.0 Hz in steps of 0.1
MESSAGE
FAULT ANALOG
INPUT 1: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 2: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 3: 0%
Range: 0 to 100% in steps of 1
MESSAGE
FAULT ANALOG
INPUT 4: 0%
Range: 0 to 100% in steps of 1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...