1–32
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Once the signal is received the motor will be started across the line. Therefore, the
following settings are left with their default values. In the
S2 SYSTEM SETUP
REDUCE
VOLTAGE STARTING
settings page:
REDUCE VOLTAGE STARTING
: “Off”
ASSIGN CONTROL RELAYS
: “Auxiliary3” (available for other use)
TRANSITION ON
: “Current Only”
ASSIGN TRIP RELAYS
: “Trip”
REDUCE VOLTAGE START LEVEL
: “100% FLA”
REDUCE VOLTAGE START TIMER
: “200 s”
1.4.5
S3 Digital Inputs Settings
The S3 settings page is for entering the characteristics of the digital inputs. In our example,
these characteristics are specified under the Control System Requirements heading.
Program the S3 settings as indicated.
Some of the functions assigned to the digital inputs of the 469 Motor Management Relay
are pre-defined functions, which can be selected from a list. There are four user-defined
functions, called General Switch A to D, associated to the assignable inputs. Set these
inputs to operate output relays, with or without delay, responding to the status change of
dry contacts connected to the digital input terminals. Use the following procedure to set
these functions:
Change the default names to meaningful values so they can be
easily identified, either via the LCD or when reviewing event reports.
Identify their asserted logic.
Define the functionality of the digital inputs.
All the other assignable input functions are pre-defined, and when selected, they can be
set to generate Trip or Alarms, as well as energize auxiliary outputs as needed.
For breaker position monitoring, set the following pre-defined Digital Input called “Starter
Status”. As per the information provided above, a 52b contact will be used, and must be
connected between terminals D16 to D23:
S3 DIGITAL INPUTS
STARTER STATUS
STARTER STATUS SW
: “Starter Auxiliary b”
To set the relay to monitor access to the station, use Assignable Input 1 as “General Switch
A”, as follows. To define the digital input, enter the following data in the
S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1
settings page.
To identify the digital input:
INPUT 1 FUNCTION
: “General Sw. A”
SWITCH NAME
: “Stn. Monitor”
To define the asserted logic:
GENERAL SWITCH A
: “Normally Open”
To define the functionality:
BLOCK INPUT FROM START
: “0 s”
GENERAL SWITCH A ALARM
: “Latched”
ASSIGN ALARM RELAYS
: “Alarm”
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...