6–32
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
Two of the 469 general counters count the number of motor starts or start attempts and
the number of Emergency Restarts performed to start a given motor over time. This may
be useful information when troubleshooting a motor failure. When either of these counters
exceeds 50000, that counter will reset to 0. This information can be cleared with the
S1 469
SETUP
INSTALLATION
RESET MOTOR INFORMATION
settings. Another of the 469
General counters will count the number of starter operations performed over time. This
counter is incremented any time the motor is stopped, either by a trip or normal stop. This
may be useful information for starter maintenance. When the counter exceeds 50000, that
counter will reset to 0. This information may be cleared with the
S1 469 SETUP
INSTALLATION
RESET STARTER INFORMATION
settings. If one of the assignable digital
inputs is programmed as Digital Counter, that counter measurement will appear here. The
counter can be reset to zero if the counter is of the incrementing type or pre-set to a
predetermined value using the
S1 469 SETUP
CLEAR DATA
PRESET DIGITAL COUNTER
settings.
6.5.3
Timers
PATH: ACTUAL VALUES
A4 MAINTENANCE
TIMERS
One of the 469 timers accumulates the total running time for the Motor. This may be useful
for scheduling routine maintenance. When this timer exceeds 100000, it will reset to 0. This
timer can be cleared using the
S1 469 SETUP
INSTALLATION
RESET MOTOR
INFORMATION
settings.
The
TIME BETWEEN STARTS TIMER
value may be viewed here. This value might be useful for
planning a motor shutdown. The
STARTS/HOUR TIMER
value is also viewable here.
TIMERS
[
]
MOTOR RUNNING
HOURS: 0 hr
Range: 0 to 100000 hrs.
MESSAGE
TIME BETWEEN STARTS
TIMER: 0 min
Range: 0 to 500 min.
MESSAGE
STARTS/HOUR TIMERS
0
0
0
0
0 min
Range: 0 to 60 min.
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...