CHAPTER 6: ACTUAL VALUES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
6–37
6.8
Diagnostics
6.8.1
Diagnostic Messages
Some actual value messages are helpful in diagnosing the cause of Trips, Alarms, or Start
Blocks. The 469 automatically defaults to the most important message. The hierarchy is
Trip and PreTrip messages, Alarm, and lastly, Start Block Lockout. To simplify things, the
Message LED (indicator) will flash, prompting the operator to press the
NEXT
key. When
NEXT
is pressed, the next relevant message is automatically displayed. The 469 cycles
through the messages with each keypress. When all of these conditions have cleared, the
469 reverts back to the normal default messages.
Any time the 469 is not displaying the default messages because other Actual Value or
settings messages are being viewed and there are no trips, alarms, or blocks, the Message
LED (indicator) will be on solid. From any point in the message structure, pressing the
NEXT
key will cause the 469 to revert back to the normal default messages. When normal default
messages are being displayed, pressing
NEXT
displays the next default message
immediately.
Example:
When an overload trip occurs, an RTD alarm may also occur as a result of the overload and
a lockout time associated with the trip. The 469 automatically defaults to the
A1 STATUS
LAST TRIP DATA
CAUSE OF LAST TRIP
actual value message and the Message LED
flashes. Pressing the
NEXT
key cycles through the time and date stamp information as well
as all of the pre-trip data. When the bottom of this queue is reached, pressing
NEXT
again
normally returns to the top of the queue. However, because an alarm is active, the display
skips to the alarm message at the top of the
A1 STATUS
ALARM STATUS
queue. Similarly,
pressing
NEXT
again skips to the
A1 STATUS
START BLOCK
RESTART BLOCK
LOCKOUT
message. Pressing
NEXT
once final time returns to the original
CAUSE OF LAST
TRIP
message, and the cycle could be repeated.
LAST TRIP DATA:
CAUSE OF LAST TRIP:
Overload
TIME OF LAST TRIP:
12:00:00.0
DATE OF LAST TRIP
Jan 01 1992
↓
↓
↓
ANALOG INPUT 4
PreTrip: 0 Units
ACTIVE ALARMS:
STATOR RTD #1
ALARM: 135°C
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...