GE Multilin
G30 Generator Protection System
B-37
APPENDIX B
B.4 MEMORY MAPPING
B
5860
...Repeated for FlexLogic Timer 13
5868
...Repeated for FlexLogic Timer 14
5870
...Repeated for FlexLogic Timer 15
5878
...Repeated for FlexLogic Timer 16
5880
...Repeated for FlexLogic Timer 17
5888
...Repeated for FlexLogic Timer 18
5890
...Repeated for FlexLogic Timer 19
5898
...Repeated for FlexLogic Timer 20
58A0
...Repeated for FlexLogic Timer 21
58A8
...Repeated for FlexLogic Timer 22
58B0
...Repeated for FlexLogic Timer 23
58B8
...Repeated for FlexLogic Timer 24
58C0
...Repeated for FlexLogic Timer 25
58C8
...Repeated for FlexLogic Timer 26
58D0
...Repeated for FlexLogic Timer 27
58D8
...Repeated for FlexLogic Timer 28
58E0
...Repeated for FlexLogic Timer 29
58E8
...Repeated for FlexLogic Timer 30
58F0
...Repeated for FlexLogic Timer 31
58F8
...Repeated for FlexLogic Timer 32
Phase Time Overcurrent (Read/Write Grouped Setting
)
5900
Phase Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5901
Phase Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5902
Phase Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5903
Phase Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5904
Phase Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5905
Phase Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5906
Phase Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5907
Phase Time Overcurrent 1 Voltage Restraint
0 to 1
---
1
F102
0 (Disabled)
5908
Phase TOC 1 Block For Each Phase (3 items)
0 to 4294967295
---
1
F300
0
590F
Phase Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5910
Phase Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5911
Reserved (3 items)
0 to 1
---
1
F001
0
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5A01
Phase Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5A02
Phase Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5A03
Phase Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5A05
Phase IOC1 Block For Each Phase (3 items)
0 to 4294967295
---
1
F300
0
5A0B
Phase Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5A0C
Phase Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5A0D
Reserved (6 items)
0 to 1
---
1
F001
0
5A13
...Repeated for Phase Instantaneous Overcurrent 2
Neutral Time Overcurrent (Read/Write Grouped Setting)
5B00
Neutral Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5B01
Neutral Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5B02
Neutral Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5B03
Neutral Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5B04
Neutral Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5B05
Neutral Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5B06
Neutral Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5B07
Neutral Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5B09
Neutral Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...