c) SNTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
SNTP PROTOCOL
The G30 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the G30 can obtain clock time
over an Ethernet network. The G30 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. UR series relays support unicast, broadcast, multicast,
and anycast SNTP functionality.
The
SNTP FUNCTION
setting enables or disabled the SNTP feature on the G30.
To use SNTP in unicast mode,
SNTP SERVER IP ADDR
must be set to the SNTP/NTP server IP address. Once this address is
set and
SNTP FUNCTION
is “Enabled,” the G30 attempts to obtain time values from the SNTP/NTP server. Since many time
values are obtained and averaged, it generally takes three to four minutes until the G30 clock is closely synchronized with
the SNTP/NTP server. It takes up to two minutes for the G30 to signal an SNTP self-test error if the server is offline.
To use SNTP in broadcast mode, set the
SNTP SERVER IP ADDR
setting to “0.0.0.0” and
SNTP FUNCTION
to “Enabled.” The
G30 then listens to SNTP messages sent to the “all ones” broadcast address for the subnet. The G30 waits up to 18 min-
utes (>1024 seconds) without receiving an SNTP broadcast message before signaling an SNTP self-test error.
The
SNTP UDP PORT NUMBER
is 123 for normal SNTP operation. If SNTP is not required, close the port by setting it to 0.
When the
SNTP UDP PORT NUMBER
is set to 0, the change takes effect when the G30 is restarted.
d) LOCAL TIME
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
LOCAL TIME
SNTP PROTOCOL
SNTP FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
SNTP SERVER IP ADDR:
0.0.0.0
Range: Standard IP address format
MESSAGE
SNTP UDP PORT
NUMBER: 123
Range: 0 to 65535 in steps of 1
LOCAL TIME
LOCAL TIME OFFSET
FROM UTC:
0.0 hrs
Range: –24.0 to 24.0 hrs in steps of 0.5
MESSAGE
DAYLIGHT SAVINGS
TIME: Disabled
Range: Disabled, Enabled
MESSAGE
DST START MONTH:
January
Range: January to December (all months)
MESSAGE
DST START DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST START DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST START HOUR:
2
Range: 0 to 23
MESSAGE
DST STOP MONTH:
January
Range: January to December (all months)
MESSAGE
DST STOP DAY:
Sunday
Range: Sunday to Saturday (all days of the week)
MESSAGE
DST STOP DAY
INSTANCE: First
Range: First, Second, Third, Fourth, Last
MESSAGE
DST STOP HOUR:
2
Range: 0 to 23
NOTE
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...