GE Multilin
G30 Generator Protection System
2-19
2 PRODUCT DESCRIPTION
2.4 SPECIFICATIONS
2
2.4SPECIFICATIONS
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
2.4.1 PROTECTION ELEMENTS
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
power system devices via communications or different output contacts. If not specified, the operate times given
here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PERCENT DIFFERENTIAL
Characteristic:
Dual slope percent differential
Minimum pickup:
0.05 to 1.00 pu in steps of 0.001
Slope 1 range:
15 to 100% in steps of 1%
Slope 2 range:
50 to 100% in steps of 1%
Kneepoint 1:
1.0 to 2.0 pu in steps of 0.001
Kneepoint 2:
2.0 to 30.0 pu in steps of 0.001
2
nd
harmonic inhibit level: 1.0 to 40.0% in steps of 0.1
2
nd
harmonic inhibit function: Adaptive, Traditional, Disabled
2
nd
harmonic inhibit mode: Per-phase, 2-out-of-3, Average
5
th
harmonic inhibit range: 1.0 to 40.0% in steps of 0.1
Operate times:
Harmonic inhibits selected: 20 to 30 ms at 60 Hz;
20 to 35 ms at 50 Hz
No harmonic inhibits selected: 5 to 20 ms
Dropout level:
97 to 98% of pickup
Level accuracy:
±0.5% of reading or ±1% of rated
(whichever is greater) for two windings
setup
RESTRICTED GROUND FAULT
Pickup:
0.005 to 30.000 pu in steps of 0.001
Dropout:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0 x CT rating: ±0.5% of reading or ±1% of rated (which-
ever is greater)
>2.0 x CT rating
±1.5% of reading
Slope:
0 to 100% in steps of 1%
Pickup delay:
0 to 600.00 s in steps of 0.01
Dropout delay:
0 to 600.00 s in steps of 0.01
Operate time:
<1 power system cycle
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
×
CT:
±1.5% of reading > 2.0
×
CT rating
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type:
Instantaneous/Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
Voltage restraint:
modifies pickup current for voltage in the
range of 0.1<V<0.9 VT Nominal in a
fixed linear relationship
PHASE/NEUTRAL/GROUND IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
×
CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
×
CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
Operate time:
<16 ms at 3
×
pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3
×
pickup at 60 Hz
(Neutral IOC)
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
NOTE
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...