5.4.5 BREAKERS
PATH: SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(4)
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
A/3P CLSD:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
A/3P OPND:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 Toperate:
0.070 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...