6
6.2.18 TELEPROTECTION CHANNEL TESTS
PATH: ACTUAL VALUES
STATUS
TELEPROT CH TESTS
The status information for two channels is shown here.
•
CHANNEL 1 STATUS
: This represents the receiver status of each channel. If the value is “OK”, teleprotection is
enabled and data is being received from the remote terminal; If the value is “FAIL”, teleprotection enabled and data is
not being received from the remote terminal. If “n/a”, teleprotection is disabled.
•
CHANNEL 1 LOST PACKETS
: Data is transmitted to the remote terminals in data packets at a rate of two packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS
CLEAR RECORDS
menu.
•
VALIDITY OF CHANNEL CONFIGURATION
: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
“FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
6.2.19 REMAINING CONNECTION STATUS
PATH: ACTUAL VALUES
STATUS
COMM STATUS REMAINING CONNECT
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
MMS TCP
— The number of IEC 61850 connections remaining.
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 1 LOST
PACKETS:
1
Range: 1 to 65535 in steps of 1
MESSAGE
CHANNEL 2
STATUS: n/a
Range: n/a, FAIL, OK
MESSAGE
CHANNEL 2 LOST
PACKETS:
1
Range: 1 to 65535 in steps of 1
MESSAGE
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
Range: n/a, FAIL, OK
COMM STATUS
REMAINING CONNECT
MMS TCP(max 5)
5
Range: 0 to 5
MESSAGE
MODBUS TCP(max 4)
4
Range: 0 to 4
MESSAGE
DNP TCP (max 2)
2
Range: 0 to 2
MESSAGE
IEC-104 (max 2)
2
Range: 0 to 2
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...