C-2
G30 Generator Protection System
GE Multilin
C.1 OVERVIEW
APPENDIX C
C
C.1.3 FILE TRANSFER BY IEC 61850
The G30 supports file transfer by IEC 61850. The approach is as follows, using the SISCO AX-S4 61850 client software as
an example.
1.
In the AX-S4 61850 Explorer window, click the
Tools
menu and access the SISCO File Transfer Utility.
2.
Select the
Remote AR Name
from the drop-down list. Available files appear in the
File Specification
area on the right
side of the window.
3.
With the
Copy
option active, select a file to transfer and click the
Go
button. The file is copied and displays in the
Local
list on the left side of the window.
4.
Repeat the process to transfer any other files.
Figure 0–1: FILE TRANSFER BY IEC 61850
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...