B-20
G30 Generator Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Source Current THD and Harmonics (Read Only) (4 modules)
2800
Ia THD for Source 1
0 to 99.9
---
0.1
F001
0
2801
Ia Harmonics for Source 1 - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
2821
Ib THD for Source 1
0 to 99.9
---
0.1
F001
0
2822
Ib Harmonics for Source 1 - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
283A
Reserved (8 items)
0 to 0.1
---
0.1
F001
0
2842
Ic THD for Source 1
0 to 99.9
---
0.1
F001
0
2843
Ic Harmonics for Source 1 - 2nd to 25th (24 items)
0 to 99.9
---
0.1
F001
0
285B
Reserved (8 items)
0 to 0.1
---
0.1
F001
0
2863
...Repeated for Source 2
28C6
...Repeated for Source 3
2929
...Repeated for Source 4
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
0 to 1
---
1
F108
0 (Off)
Expanded Contact Input/Output States (Read Only)
2D00
Contact Input States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
2D80
Contact Output States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
2E00
Virtual Output States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (32 items)
0 to 1
---
1
F155
0 (Offline)
2F80
Remote Input States, one per register (64 items)
0 to 1
---
1
F108
0 (Off)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
0 to 65535
---
1
F001
0
3001
Oscillography Available Records
0 to 65535
---
1
F001
0
3002
Oscillography Last Cleared Date
0 to 400000000
---
1
F050
0
3004
Oscillography Number Of Cycles Per Record
0 to 65535
---
1
F001
0
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
0 to 1
---
1
F126
0 (No)
3011
Oscillography Clear Data
0 to 1
---
1
F126
0 (No)
Oscillography Analog Values (Read Only)
3012
Oscillography Number of Triggers
0 to 32767
---
1
F001
0
User-Programmable Fault Report Commands (Read/Write Command)
3060
User Fault Report Clear
0 to 1
---
1
F126
0 (No)
User-Programmable Fault Report Actual Values (Read Only)
3070
Newest Record Number
0 to 65535
---
1
F001
0
3071
Cleared Date
0 to 4294967295
---
1
F050
0
3073
Report Date (10 items)
0 to 4294967295
---
1
F050
0
User-Programmable Fault Report (Read/Write Setting) (2 modules)
3090
Fault Report 1 Fault Trigger
0 to 4294967295
---
1
F300
0
3092
Fault Report 1 Function
0 to 1
---
1
F102
0 (Disabled)
3093
Fault Report 1 Prefault Trigger
0 to 4294967295
---
1
F300
0
3095
Fault Report Analog Channel 1 (32 items)
0 to 65536
---
1
F600
0
30B5
Fault Report 1 Reserved (5 items)
---
---
---
F001
0
30BA
...Repeated for Fault Report 2
Modbus File Transfer (Read/Write)
3100
Name of file to read
---
---
---
F204
(none)
Modbus File Transfer Values (Read Only)
3200
Character position of current block within file
0 to 4294967295
---
1
F003
0
3202
Size of currently-available data block
0 to 65535
---
1
F001
0
3203
Block of data from requested file (122 items)
0 to 65535
---
1
F001
0
Security (Read/Write Setting)
3280
Administrator Alphanumeric Password Setting
---
---
---
F202
(none)
Security (Read Only)
328A
Administrator Alphanumeric Password Status
0 to 1
---
1
F102
0 (Disabled)
Table B–10: MODBUS MEMORY MAP (Sheet 12 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...