GE Multilin
G30 Generator Protection System
5-43
5 SETTINGS
5.2 PRODUCT SETUP
5
The fixed GOOSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION
TRANSMISSION
FIXED GOOSE
These settings are applicable to fixed (DNA/UserSt) GOOSE only.
The
GOOSE ID
setting represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE
message. This string identifies the GOOSE message to the receiving device. In revisions previous to 5.0x, this name string
was represented by the
RELAY NAME
setting.
The
DESTINATION MAC
setting allows the destination Ethernet MAC address to be set. This address must be a multicast
address; the least significant bit of the first byte must be set. In G30 releases previous to 5.0x, the destination Ethernet
MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of
the G30) and setting the multicast bit.
The
GOOSE VLAN PRIORITY
setting indicates the Ethernet priority of GOOSE messages. This allows GOOSE messages to
have higher priority than other Ethernet data. The
GOOSE ETYPE APPID
setting allows the selection of a specific application
ID for each GOOSE sending device. This value can be left at its default if the feature is not required. Both the
GOOSE VLAN
PRIORITY
and
GOOSE ETYPE APPID
settings are required by IEC 61850.
FIXED GOOSE
GOOSE FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
GOOSE ID:
GOOSEOut
Range: 65-character ASCII string
MESSAGE
DESTINATION MAC:
000000000000
Range: standard MAC address
MESSAGE
GOOSE VLAN PRIORITY:
4
Range: 0 to 7 in steps of 1
MESSAGE
GOOSE VLAN ID:
0
Range: 0 to 4095 in steps of 1
MESSAGE
GOOSE ETYPE APPID:
0
Range: 0 to 16383 in steps of 1
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...