GE Multilin
G30 Generator Protection System
5-135
5 SETTINGS
5.5 FLEXLOGIC
5
ELEMENT:
Teleprotection
channel tests
TELEPRO CH1 FAIL
TELEPRO CH2 FAIL
TELEPRO CH1 ID FAIL
TELEPRO CH2 ID FAIL
TELEPRO CH1 CRC FAIL
TELEPRO CH2 CRC FAIL
TELEPRO CH1 PKT LOST
TELEPRO CH2 PKT LOST
Channel 1 failed
Channel 2 failed
The ID check for a peer relay on channel 1 has failed
The ID check for a peer relay on channel 2 has failed
CRC detected packet corruption on channel 1
CRC detected packet corruption on channel 2
CRC detected lost packet on channel 1
CRC detected lost packet on channel 2
ELEMENT:
Teleprotection
inputs/outputs
TELEPRO INPUT 1-1 On
↓
TELEPRO INPUT 1-16 On
TELEPRO INPUT 2-1 On
↓
TELEPRO INPUT 2-16 On
Flag is set, Logic =1
↓
Flag is set, Logic =1
Flag is set, Logic =1
↓
Flag is set, Logic =1
ELEMENT:
Thermal overload
protection
THERMAL PROT 1 PKP
THERMAL PROT 1 OP
Thermal overload protection 1 picked up
Thermal overload protection 1 operated
THERMAL PROT 2
Same set of operands as shown for THERMAL PROT 1
ELEMENT
Trip bus
TRIP BUS 1 PKP
TRIP BUS 1 OP
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
TRIP BUS 2 to 6
Same set of operands as shown for TRIP BUS 1
ELEMENT:
Underfrequency
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
Underfrequency 1 has picked up
Underfrequency 1 has operated
Underfrequency 1 has dropped out
UNDERFREQ 2 to 6
Same set of operands as shown for UNDERFREQ 1
ELEMENT:
Volts per hertz
VOLT PER HERTZ 1 PKP
VOLT PER HERTZ 1 OP
VOLT PER HERTZ 1 DPO
The volts per hertz element 1 has picked up
The volts per hertz element 1 has operated
The volts per hertz element 1 has dropped out
VOLT PER HERTZ 2
Same set of operands as VOLT PER HERTZ 1
ELEMENT:
Transformer percent
differential
XFMR PCNT DIFF PKP A
XFMR PCNT DIFF PKP B
XFMR PCNT DIFF PKP C
XFMR PCNT DIFF 2ND A
XFMR PCNT DIFF 2ND B
XFMR PCNT DIFF 2ND C
XFMR PCNT DIFF 5TH A
XFMR PCNT DIFF 5TH B
XFMR PCNT DIFF 5TH C
XFMR PCNT DIFF OP
XFMR PCNT DIFF OP A
XFMR PCNT DIFF OP B
XFMR PCNT DIFF OP C
Transformer percent differential protection has picked up in phase A
Transformer percent differential protection has picked up in phase B
Transformer percent differential protection has picked up in phase C
The 2nd harmonic of transformer percent differential has blocked phase A
The 2nd harmonic of transformer percent differential has blocked phase B
The 2nd harmonic of transformer percent differential has blocked phase C
The 5th harmonic of transformer percent differential has blocked phase A
The 5th harmonic of transformer percent differential has blocked phase B
The 5th harmonic of transformer percent differential has blocked phase C
At least one phase of transformer percent differential has operated
Phase A of transformer percent differential has operated
Phase B of transformer percent differential has operated
Phase C of transformer percent differential has operated
FIXED OPERANDS
Off
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1
On
Cont Ip 2
On
↓
Cont Ip 1
Off
Cont Ip 2
Off
↓
Cont Ip 96
On
Cont Ip 96
Off
(will not appear unless ordered)
(will not appear unless ordered)
↓
(will not appear unless ordered)
(will not appear unless ordered)
↓
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs
Cont Op 1 Closed
Cont Op 1 IOn
Cont Op 1 VOn
Cont Op 1 VOff
Contact output is closed
Current is flowing through the contact
Voltage exists across the contact (present for contact outputs equipped with
monitoring)
Voltage exists across the contact (present for contact outputs equipped with
monitoring)
Cont Op 2 to 64
Same set of operands as shown for Cont Op 1
INPUTS/OUTPUTS
Direct inputs
DIRECT INPUT 1 On
↓
DIRECT INPUT 32 On
Flag is set, logic=1
↓
Flag is set, logic=1
Table 5–17: G30 FLEXLOGIC OPERANDS (Sheet 6 of 8)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание G30
Страница 10: ...x G30 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 G30 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 414: ...5 274 G30 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 456: ...8 2 G30 Generator Protection System GE Multilin 8 1 DIRECTIONAL PRINCIPLE 8 THEORY OF OPERATION 8 ...
Страница 470: ...9 14 G30 Generator Protection System GE Multilin 9 1 SETTING EXAMPLE 9 APPLICATION OF SETTINGS 9 ...
Страница 484: ...11 12 G30 Generator Protection System GE Multilin 11 6 DISPOSAL 11 MAINTENANCE 11 ...
Страница 512: ...A 28 G30 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 620: ...B 108 G30 Generator Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 666: ...E 10 G30 Generator Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 678: ...F 12 G30 Generator Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 687: ...GE Multilin G30 Generator Protection System H 7 APPENDIX H H 2 ABBREVIATIONS H Z Impedance Zone ...